41DVN / DVSN Direct Vent Gas Fireplace
20009999
Mantels
The height that a combustible mantel is fitted above the 
fireplace is dependent on the depth of the mantel. This 
also applies to the distance between the mantel leg (if 
fitted) and the fireplace.
For the correct mounting height and widths, refer to 
Figures 4a, 4b and the Mantel Chart below.
The distances and reference points are not affected by 
the fitting of a bay window front trim kit.
Noncombustible mantels and legs may be installed at 
any height and width around the appliance. When using 
paint or lacquer, it must be heat resistant to prevent 
discoloration. 
Clearance to Combustibles
Top of unit to ceiling ................................. 36” (914 mm)
Front of unit to combustibles ................... 36” (914 mm)
Appliance
 
Top  ......................................................... 0” (0 mm)
 
Bottom ..................................................... 0” (0 mm)
 
Side ......................................................... 0” (0 mm)
 
Back ........................................................ 0” (0 mm)
Venting
Concentric sections of DV Vent ................... 1” (25 mm)
Nonconcentric sections of DV Vent 
 
Sides and bottom .................................. 1” (25 mm)
 
Top ........................................................ 2” (51 mm)
Flex Vent .................................................. 7/8” (22 mm)
J
F
G
H
I
Mantel
Leg
CFM164a
Mantel Leg Chart
06/22/01   sta
Black 
Surround 
Face
CFM164a
CFM170
DV Builder Front 
View
O
N
M
L
K
Side of 
Combustion Chamber
CFM170
Fig. 4b   Combustible mantel leg minimum installation.
 
 
Mantel 
 
Mantel Leg from Side
  Ref. 
Leg Depth 
Ref. 
of Comb. Opening
 
10” (254 mm) 
11¹⁄₂” (292 mm)
 
8” (203 mm) 
9¹⁄₂” (241 mm)
 
6” (152 mm) 
7¹⁄₂” (191 mm)
 
4” (101 mm) 
5¹⁄₂” (140 mm)
 
2” (51 mm) 
3¹⁄₂’” (89 mm)
Y
E
A
B
C
D
F
Y
B
X
LU584-1
Locating unit
2/4/99   djt
A) Flat on wall  
B) Cross corner 
C)  **Island
D) Room divider 
E) Flat on wall corner 
F)  Chase installation
Y) Refer to “Clearance to Combustibles” Section
Note (Fig. 3):  
** Island (C) and Room Divider (D) installation is possible as 
long as the horizontal portion of the vent system (X) does not 
exceed 20’ (610 cm).  See details in Venting Section.
Locating Your Fireplace
Fig. 3  Locating Gas Fireplace
LU584-1
A B C D E
V
W
X
Y
Z
Fireplace
CFM146
DV Mantel Chart
7/5/01   sta
Louvre Assembly 
Top
Top of Combustion 
Chamber
Bottom of Door Trim
CFM146
Fig. 4a  Combustible mantel minimum installation.
Mantel Chart
 
 
Mantel S
helf 
 
Mantel from Top
  Ref. 
or Breast Plate 
Ref. 
of Comb. Chamber 
 
 
Depth
 
10” (254 mm) 
19” (483 mm)
 
8” (203 mm) 
17” (432 mm)
 
6” (152 mm) 
15” (381 mm)
 
4” (101 mm) 
13” (330 mm)
 
2” (51 mm) 
11” (279 mm)
Maintain Minimum 
3/4” (19 mm) 
Clearance to 
Combustibles