HEARTH ExTENSION
A hearth extension projecting a minimum of 
20" in front of and a minimum of 12" beyond 
each side of the fireplace opening is required 
to  protect  combustible  floor  construction 
in  front  of  the  fireplace.  Fabricate  a  hearth 
extension using a material which meets the 
following  specifications:  a  layer  of  noncom-
bustible, inorganic material having a thermal 
conductivity of K=0.84 BTU IN/FT, HR. F (or 
less) at 1" thick. For example, if the material 
selected has a K factor of 0.25, such as glass 
fiber, the following formula would apply:
 
0.25 x 1.0" = 0.30" thickness required
 
0.84
Thermal conductivity "K" of materials can be 
obtained from the manufacturer or supplier of 
the noncombustible material. If the hearth ex-
tension is to be covered, use noncombustible 
material  such  as  tile,  slate,  brick,  concrete, 
metal,  glass,  marble,  stone,  etc.  Provide  a 
means to prevent the hearth extension from 
shifting and seal gap between the fireplace 
frame and hearth extension with a noncom-
bustible material (see Figure 3). 
 WARNING: Hearth extension 
is to be installed only as shown 
in Figure 3.
installation
Continued
Figure 3 - Hearth Extension
Seal Gap
Fireplace Front
Ember Protector
Fireplace Front 
Raised Hearth
Fireplace Front 
Elevated
Ember Protector
Ember Protector
Seal Gap
Hearth 
Extension
MANTELS
A  mantel  may  be  installed  if  desired  (see 
Figure  4).  Woodwork  such  as  wood  trims, 
mantels  or  any  other  combustible  material 
projecting  from  the  front  face  must  not  be 
placed  within  12"  of  the  fireplace  opening. 
Combustible  materials  above  12"  and  pro-
jecting  more  than  1 
1
/
2
"  from  the  fireplace 
must  not  be  placed  less  than  15"  from  the 
top opening of the fireplace (NFPA STD 211, 
Sec. 7-3.3.3).
Mantels  or  any  other  combustible  material 
also  may  come  up  to  the  side  edge  of  the 
black metal face of the fireplace just as long 
as the projection from the front face fall within 
the limit shown in Figure 4.
12 
1
/
4
" Ref.
15" Min.
12" Min.
1
1
/
2
" Max.
3" Nom.
33°
Combustible 
Material
Safe 
Zone for 
Projection of 
Combustible 
Materials
Fireplace Opening
Upper 
Section of 
Fireplace
Figure 4 - Mantel Clearances to 
Combustible Material
6"
Ref.
OPTIONAL OUTSIDE AIR KIT 
(MoDeL Ak4/Ak4f)
Installation of an outside air kit should be per-
formed during rough framing of fireplace due 
to nature of it's location. Outside combustion 
air is accessed through a vented crawl space 
(AK4F) or through a sidewall (AK4). This fire-
place is equipped with a barometric damper 
which  allow  outside  air  to  flow  into  fireplace 
automatically when needed.