MS4209F, MS4309F, MS4709F, MS4809F, MS8209F, MS8309F FAST-ACTING, TWO-POSITION ACTUATORS
Automation and Control Solutions
Honeywell International Inc.
Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN  55422
Toronto, Ontario  M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2007 Honeywell International Inc.
63-1292—6    C.H.  Rev. 04-07 
Cycling Requirements:
!
Prolonged holding-period (1 year) testing of these 
actuators has been performed with no spring return 
failures. The actuator and the internal spring are designed 
to require no special cycling during long-term holding.
!
Honeywell recommends following all local, state and 
national codes for periodic testing of the entire smoke 
control system. Refer to National Fire Protection 
Association (NFPA) National Fire Codes
®
: NFPA90A, 
NFPA92A and NFPA92B for your application.
!
NFPA recommends periodic examination of each fire/
smoke damper (semi-annually or annually) to ensure 
proper performance.
Mounting:
!
3/8 to 1/2 in. square or round damper shafts.
!
The actuator can be mounted with shaft in any position.
!
Secure hub to shaft with:
!
MS4709, MS4809: Four 3 mm set screws. 
Use 3 mm Allen wrench to tighten set screws.
!
MS4209, MS4309, MS8209, MS8309: 1/4-28 UNF set 
screws. Use 1/8 Allen wrench to tighten set screws.
Environmental Protection Ratings:
Approvals:
Accessories (not supplied with actuator):
!
201391 Shaft Adapter for 3/8 in. shafts.
!
205649 Mounting Bracket.
!
32003532-002 Dual Auxiliary Switch Package for 
UL555(S) applications.
Fig. 1. Typical 24 Vac wiring.
Fig. 2. Typical 120 Vac wiring.
Fig. 3. Typical 230 Vac wiring.
Dimensions:
National Fire Codes
®
 is a registered trademark of the National Fire Protection Association (NFPA).
MS4209, MS4309
MS4709, MS4809, 
MS8209, MS8309
NEMA1
X
X
IP54
X
MS4209, MS4309
MS4709, MS4809, 
MS8209, MS8309
UL/cUL
X
X
UL873 
Plenum Rating, 
File No. E4436; 
Guide No. XAPX
X
X
CE
X
C-TICK
X
L1 
24 VAC
L2
RED
BLACK
M17585A
(   )
(   )
L1 
120 VAC
L2
WHITE
BLACK
M17589A
(   )
(   )
L1 
230 VAC
L2
BLUE
BROWN
M17588A
(   )
(   )
2 (51)
1 (25)
5/8 
(17)
6 3/8
(161)
7 1/2 
(192)
4 (102)
7/8 (22)
5 1/8 (129)
2 (51)
3 5/16 (84)
1/16 (2)
M17508