NOTE:
 For best performance, the AC cable 
voltage drop should not exceed 10 volts, or 
10 percent at 115 volts and 5 percent at 230 volts. 
Make sure that even with the AC voltage drop, the 
AC voltage always stays in the operating windows.
The minimum electrical service amperage required by 
an MJF-212A system is the sum of each loudspeaker’s 
maximum long-term continuous current. An additional 30 
percent above the minimum amperage is recommended to 
prevent peak voltage drops at the service entry.
ElECTRICAl SAfETy ISSUES
Pay close attention to these important electrical and safety 
issues.
 
 
CAUTION:
 In the unlikely event that the 
circuit breakers on the monitor’s user panel 
trip (the white center buttons pop out), disconnect 
the AC power cable. Do not reset the breakers with 
the AC connected. Contact Meyer Sound for repair 
information.
 
CAUTION: 
The MJF-212A monitor requires 
a grounded connection. Always use a 
grounded outlet and plug.
 
CAUTION: 
Do not use a ground-lifting 
adapter or cut the AC cable ground pin.
 
CAUTION: 
Do not exceed the current 
capability of the monitor’s 20-amp AC 
connector. When looping, always take into account 
the current draw of all loudspeakers on the circuit, 
including the first unit. 
 
CAUTION: 
Make sure that the power plug 
is appropriate for the AC power at the site 
where you will operate the MJF-212A monitor. In 
addition, the connector must be rated for the total 
load of 
all MJF-212A loudspeakers looped to the 
same power plug.