Omron C200HG Manuale Utente
484
10-3-25
ERROR READ –– MF
Reads and clears errors in the PC. Also checks whether previous errors have
been cleared.
been cleared.
Command Format
@
M
F
x 10
0
x 10
1
x 10
1
x 10
0
↵
Node no.
Header
code
code
Terminator
FCS
Error clear
For the “error clear” parameter, specify 01 to clear errors and 00 to not clear er-
rors (BCD). Fatal errors can be cleared only when the PC is in PROGRAM
mode.
rors (BCD). Fatal errors can be cleared only when the PC is in PROGRAM
mode.
Response Format
@
M
F
x 10
0
x 10
1
x 16
1
x 16
0
x 16
3
x 16
2
x 16
1
x 16
0
x 16
3
x 16
2
x 16
1
x 16
0
↵
Node no.
Header
code
code
End code
Error information
(1st word)
(1st word)
Terminator
FCS
Error information
(2nd word)
(2nd word)
15
14
13
12
11
10
9
8
0
0
x 16
3
x 16
2
7
6
5
4
x 16
1
3
2
1
0
x 16
0
ON: Battery error (Error code F7)
ON: Special I/O Unit error
ON: System error (FAL)
ON: Memory error (Error code F1)
ON: I/O bus error (Error code C0)
ON: PC link error
ON: Host Link Unit transmission error
ON: No end instruction error (FALS)
ON: System error (FALS)
Bit
1st word
0 0 0: CPU Rack
0 0 1: Expansion I/O Rack 1
0 1 0: Expansion I/O Rack 2
0 1 1: Expansion I/O Rack 3
0 0 1: Expansion I/O Rack 1
0 1 0: Expansion I/O Rack 2
0 1 1: Expansion I/O Rack 3
(Data from I/O bus)
0 1: Group 2 (data bus failure)
0 1: Group 2 (data bus failure)
15
14
13
12
11
10
9
8
0
0
0
x 16
3
x 16
2
7
6
5
4
x 16
1
3
2
1
0
x 16
0
FAL, FALS No. (B CD00 to 99)
ON: I/O verify error (Error code F7)
ON: Cycle time overrun (Error code F8)
ON: I/O Unit overflow (Error code E1)
ON: I/O setting error (Error code E0)
ON: Remote I/O error (Error codes B0 to B3)
Bit
2nd word
Host Link Commands
Section 10-3