INSTALLATION INSTRUCTIONS
62-0258
T7351 Commercial Programmable
Thermostat
FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/HEAT PUMP 
SYSTEMS
APPLICATION
The T7351 Commercial Programmable Thermostat 
controls 24 Vac commercial single zone heating, 
ventilating and air conditioning (HVAC) equipment. The 
T7351 consists of a thermostat and subbase. The 
thermostat includes the display and keypad for 7-day 
programming. The subbase includes equipment control 
connections. The subbase mounts on the wall and the 
thermostat mounts to the subbase.
MERCURY NOTICE
If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash. Dispose of properly.
Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of an old control. If you have 
questions, call Honeywell Customer Care Center 
at 1-800-468-1502.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.
2. Check ratings given in instructions and on the 
product to ensure the product is suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage 
Hazard. Can shock individuals or short 
equipment circuitry.
Disconnect power supply before installation.
Location
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 
behind the thermostat.
IMPORTANT
To avoid electrical interference, which can 
cause erratic performances, keep wiring runs as 
short as possible and do not run thermostat 
wires adjacent to the line voltage electrical dis-
tribution systems. Use shielded cable. The 
cable shield must be grounded only at the con-
trolled equipment case.
Subbase
WHEN USED TO SENSE ROOM TEMPERATURE
Install the thermostat about 5 ft. (1.5m) above the floor in 
an area with good air circulation at average temperature. 
(See Fig. 1.)
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and 
humidity) sensor(s) to sense ambient conditions, install 
the thermostat in an area that is accessible for setting 
and adjusting the temperature and settings.
Install the remote-mounted sensor(s) about 5 ft. (1.5m) 
above the floor in an area with good air circulation at 
average temperature (See Fig. 1).
If multiple remote sensors are required, they must be 
arranged in a temperature averaging network consisting 
of four sensors (See Fig. 2).
NOTE: Only T7770 models with no setpoint adjustment 
can be used for temperature averaging.