CRS ZONE TM:  
4
 Cross Zone Time
Enter the time allowed between zone faults. When zones are cross zoned, the same
zone or a second cross zoned zone must fault within this time in order for an alarm 
report for both zones to be sent to the receiver.  If the cross zone time expires 
without the second zone faulting, only a zone fault from the first zone is reported.
Cross-zone time can be from 4 to 250 seconds. Entering 0 (zero) disables this
function.  Default is 4.  See the Appendix.
9.7 
RETARD DELAY:  10
 Zone Retard Delay
Enter the retard time assigned to Fire, Supervisory, Auxiliary 1, Auxiliary 2, Arming, 
and Panic type zones.  The retard delay only functions when the zone is shorted.  
The zone must remain shorted for the entire length of the Retard Delay before being 
recognized by the panel. The Zone Retard Delay can be from 1 to 250 seconds.
Entering a 0 (zero) disables this function.
9.8 
PWR FAIL HRS: 
1
 Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off for
the length of the programmed delay time, an AC power failure report is sent to the 
receiver. The delay time can be from 1 to 15 hours. Entering a 0 (zero) sends the
power failure report after a 15-second delay. The default setting is 1.
   
9.9 
SWGRBYPS TRIPS:  1
 Swinger Bypass Trips
Enter the number of times (1 or 2) a zone can go into an alarm or trouble condition
within one hour be fore being auto matically bypassed.  You can select one or two 
trips.  Bypassed zones are auto matically reset when the area they are assigned to is 
disarmed. All 24-hour zones are reset when any area of the system is dis armed. A
programming Stop operation restores a bypassed zone. Entering 0 (zero) disables
this function.  Default is 1.
How it works
The panel hour timer starts at 59 minutes past the hour. If the hour timer expires
before the trip counter is exceeded, the trip counter returns to 0 (zero). If the trip
counter is exceeded before the hour expires, the zone is auto matically bypassed by 
the panel.  A Bypass Re port is sent to the receiver if Bypass Re ports is YES.
9.10 
RST SBYP  NO  YES
 Reset Swinger Bypass
When YES is selected, an auto matically bypassed zone is reset if it remains in a
normal condition for one complete hour after being bypassed.  A report of the 
automatic reset is sent to the receiver if Bypass Reports has been se lected as YES.  
Default is NO.
9.11 
TIME CHG   NO  YES
 Time Zone Changes
This function allows the panel to request automatic time changes from the DMP 
SCS-1R Receiver on Path 1. For the receiver to send time changes, it must be
programmed to send time changes and must be receiving time change updates from 
the network automation computer at least every 24 hours.  Default is YES.
HRS FROM GMT: 
6
 
When time zone is programmed YES, enter the number (0-23) that indicates the
Greenwich Time zone (GMT) where the panel is located. The default is 6.