Problem
Possible Cause
Possible Solution
Possible Solution
Possible Solution
Compressor 
attempts to 
start, or runs for 
short periods 
only. Cycles on 
overload.
Compressor attempts to start 
before system pressures are 
equalized.
Allow a minimum of 3 minutes to allow pressures 
to equalize before attempting to start. 
Low or fluctuating voltage.
Check voltage with unit operating. Check for 
other appliances on the circuit. Unit should be on 
separate circuit for proper voltage, and be fused 
separately
Incorrect wiring
Connect per appropriate wiring diagram
Shorted or incorrect capacitor
Replace capacitor
Restricted or low air flow through 
condenser coil
Check motor fan blade.
Compressor running abnormally 
hot
Check for refrigerant restriction, blocked airflow, 
loose wires at compressor terminals  and fan 
motor capacitor voltage.
Overload opens too soon.
Change compressor if all other corrections above 
are normal.
Problem
Possible Cause
Compressor does 
not start - fan 
motor runs.
Thermostat contacts not closing.
Check continuity of thermostat at coldest setting. If 
compressor runs, replace thermostat.
Low voltage supply. 
Check for nameplate voltage. Provide proper 
voltage.
Switch (On-Off) inoperative.
Test for continuity.
Defective capacitor.
Test with analyzer, replace if needed.
Compressor internal overload 
open.
Check voltage at compressor terminals. If voltage 
is satisfactory, replace compressor.
Solid state relay open.
Replace relay.
Open or shorted compressor 
windings.
Check windings for continuity and resistance. If 
open, replace compressor.
Problem
Possible Cause
Does not cool, or 
cools only slightly.
Thermostat open or inoperative.
Set to coldest position. Test thermostat and 
replace if necessary.
Dirty air filter.
Clean as recommended in Owner’s Manual.
Dirty or plugged condenser or 
evaporator coil.
Clean coils.
Poor air circulation in area being 
cooled.
Adjust air louvers. Check application. Check for 
dirty filter or evap coil. Check fan motor. Correct as 
needed.
Low capacity - undercharge.
Check for leak and make necessary repairs.
Compressor not pumping properly. Replace compressor.
TROUBLESHOOTING
NOTE: If Inside Coil Freezes Up
Your Friedrich Hazardgard is designed not to freeze with outdoor temperatures as low as 45°F (7°C). If the indoor coil should 
ice over while cooling, set the thermostat to the warmest position until the ice on the coil is gone. Setting the thermostat to a 
slightly warmer position will probably keep ice from forming on the coil. A dirty filter will contribute to icing.
25