SK-5208 Basic Operating Instructions P/N 151214 Rev. A
These instructions must be framed and displayed next to the panel in accordance with NFPA 
72 fire code for Local Fire Alarm System.
    
How To 
Do This
Comments
Press
Display Message
Press
Test the system
 
6\VWHP 7HVW
(QWHU &RGH
Enter Code
The system will perform a display lamp test and a 
communication test.
Reset Alarms
 
5HVHW $ODUP
(QWHU &RGH
Enter Code
Resets system.
Reset the Dialer
 
5HVHW 'LDOHU
(QWHU &RGH
Enter Code
Resets the dialer and aborts the call to central station.
Display History 
Events
 
+LVWRU\ (YHQWV
(QWHU &RGH
Enter Code
Displays the panel history, which includes alarms, 
supervisories, troubles, reports, time and date changes, etc.
Show Status
 
6KRZ 6WDWXV
(QWHU &RGH
Enter Code
View existing system status. List Alarms first, 
supervisories and then troubles.
Silence Troubles or 
Alarms
  
or
6LOHQFH
(QWHU &RGH
Enter Code
Disable/Enable a Zone Zone # + 
 
'LVDEOH =RQH
(QWHU &RGH
Enter Code
Repeat the process to enable the zone.
Disable/Enable NAC
  
NAC 
'LVDEOH 1$&
(QWHU &RGH
Enter Code
Repeat the process to enable the NAC.
Conduct a Fire Drill
 
 
)LUH 'ULOO
(QWHU &RGH
Enter Code
To End the Fire Drill press 
 then code.
Reset Detectors
 
 
5VW 6PN 3ZU
(QWHU &RGH
Enter Code
Resets all smoke detector power.
Walk Test the System
 
 
:DON 7HVW
(QWHU &RGH
Enter Code
To End the Walk Test press 
.
Menu of Options
Press  
or  
to scroll trough list.
Enter Installer
Code
To exit press 
 or wait 15 seconds.
Acknowledge Events
Events can be acknowledged by pressing the 
 button. No code is required to acknowledge events. The status LEDs 
(Alarm, Supervisory and Trouble) will flash when an un-acknowledged alarm, supervisory, or trouble condition exists. 
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble LED) stop flashing and turn on 
steady. When viewing system status the LCD displays “Acked” for each individual event once it has been acknowledged. The 
control panel piezo will silence after all alarms have been acknowledged.
Note:  The control panel piezo will continue to sound for Supervisories and Troubles even after the event has been 
acknowledged. Supervisories and troubles will silence once the event is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged events in the history buffer will be 
preceded with an asterisk “*”.
LEDs Meaning
LED
Status
Condition
ALARM (red)
Off
Normal condition
On
System in alarm.
Flashing
LED will flash when a alarm condition exists that has not been acknowledged.
SUPERVISORY (yellow)
Off
Normal condition
On
If a supervisory condition exist on the system.
Flashing
LED will flash when a supervisory condition exists that has not been acknowledged.
TROUBLE (yellow)
Off
Normal condition
On
Trouble condition exists
Flashing
LED will flash when a trouble condition exists that has not been acknowledged.
SILENCED (yellow)
Off
Normal condition.
On
Alarm or trouble condition has been silenced but condition still exists.
AC (green)
On
Panel is running on AC (normal condition); standby battery fully charged.
Off
Panel has lost all power.
Flashing
Panel is running on battery power only or AC power only.
0
1
3
5
6
7
1
0
2
0
2
1
2