49
Figure 13. Diagram of Smoke Detector Locations
Appendix A:
Troubleshooting
System Status
How to clear SYSTEM STATUS (Alarm Memory)
From a disarmed state press SYSTEM STATUS, listen to the status message, then press
DISARM.
DISARM.
Panel announces Siren 1 failure or Siren 2 failure.
•
Turn option 53 off if a hardwire siren or sensor is not connected.
•
Check for the correct end-of-line resistor in HWIN 1 and 2 circuits.
Panel announces Low Battery.
•
Check that panel backup battery is connected.
Panel announces Option 50 Detected.
•
Option 50 is RF jam detect. The control panel has detected RF interference.
Living
Room
Room
Dining
Room
Room
Basement
x
H
Hall
Bedroom
Bedroom
Living
Room
Room
Recreation
Room
Room
Basement
Hall
Bedroom
Bedroom
Living
Room
Room
Dining
Room
Room
Hall
Bedroom
Bedroom
Bedroom
Kitchen
A smoke detector sho uld
be loc at ed on eac h le ve l.
Smoke detectors should
be located between t he
sleeping area and the rest
of the f amily living unit.
NOTE: Do not install smoke detectors wher e normal ambient t emperatures are above
100°F or b elow 40°F. A lso, d o not locate d etectors in front of AC/ H eat
registers o r other lo cations where normal air circulatio n will keep smoke
fr om e n terin g t he de t ect or.
NOTE: Additional information on household fire war ning is available at n omin al
cost f rom: T he National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269. Request Standard No. NFPA74.
H
x
Living
Room
Room
Bedroom
Bedroom
Bedroom
Dining
Room
Room
Kitchen
TV
Room
Room
In f amily living units with more
than o ne sleepin g area, locate a
smoke detector at each area.
H
NOTE : Ceilin g-mo un ted sm oke detectors should be lo cated in t he c e nt er o f t he ro om
o r hall, or not less than 4 inches from t he wall. When t he detector is mounted
o n the wall, t he top o f the detector should be 4 t o 12 inches from t he ceiling.
Required smoke detector
Heat d et ector
Indicates smoke detector is option al if door is not provid ed b et ween
basement and recreation rooms.
8557144a