Configuring the system
Setting
Linked control of air conditioning units
By setting conditions for input points and output points, you can perform linked control of air conditioning 
units (indoor units and outdoor units).
For example, you can make a setting so that all indoor units stop operating at the same time (output point) 
in response to a fire alarm going off (input point).
4
Select the input point border (4-1) and 
touch [Set] (4-2).
 
z
The “Input point settings” dialogue is displayed.
4-
1
4-
2
5
Select the input target from the list.
 
z
Input targets include air conditioner alarms, digital input/
output devices, indoor units (individual and control groups).
5
Continued on next page
1
Touch [System Settings] in “Settings”.
 
z
The “System settings” screen is displayed.
1
2
Touch [Event control].
 
z
The “Event control” screen is displayed.
2
3
Select an event name.
 
z
Use     to select the name to register the event.
 
z
You can change the event names. (→ “Changing an event 
name” (P.167))
3