Settings for energy saving
Energy saving
Control operation at regular intervals 
[I/D unit cyclic]
This type of control rotates through the set times slots at the specified intervals (3 minutes, 4 minutes, 
5 minutes), evenly operating the indoor units in the control groups using the settings (OFF, thermostat, 
mode, set temperature) and recovering.
3
Put a check mark in the “Select” column 
(3-1), and touch [Set.] (3-2).
 
z
The “Setting” dialogue is displayed.
3-
1
3-
2
4
Change the settings.
Item
Explanation
Control Gr. 1-10
Press     to set the control group that 
the indoor unit is to be allocated to. (Up to 
10 groups)
Set from “Gr.1” to “Gr.10”.
Ope.
Operation of the indoor units is stopped.
Set either [OFF] or [----]*.
T/S
The thermostat is set to off forcibly.
Select between [T/S OFF] and [----]*.
Continued on next page
1
Touch [Demand setting] in 
“EnergySaving”.
1
2
Touch [I/D unit cyclic].
 
z
The “I/D unit cyclic” screen is displayed.
2
 
y
When using cycling control at 5 minute intervals on the indoor 
units in control groups 1 to 5
Control groups 1 to 3 are “T/S OFF” and control groups 4 and 5 are 
“Fan”, and if the interval is “5 min.”, the cycling control happens at 
5 minute intervals.
5 min.
5 min.
5 min.
5 min.
5 min.
Thermostat 
forced OFF
Thermostat 
forced OFF
Normal 
operation
Normal operation
Normal operation
Normal operation
Normal operation
Normal operation
Normal 
operation
Fan
Fan
Thermostat 
forced OFF
Normal operation
Control group 1
Control group 2
Control group 3
Control group 4
Control group 5