Puls ML60.241 Power Supply Guida Specifiche
ML60.241
MiniLine
24V,
2.5A,
S
INGLE
P
HASE
I
NPUT
14. E
NVIRONMENT
Operational temperature
*)
-10°C to +70°C (-32°F to 158°F)
reduce output power according Fig. 14-1
Storage temperature
-40°C to +85°C (-40°F to 185°F)
for storage and transportation
Output de-rating
1.5W/°C
60-70°C (140°F to 158°F)
Humidity
**)
5 to 95% r.H.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
2 hours / axis
IEC 60068-2-6
Shock
15g 6ms, 10g 11ms
3 bumps / direction, 18 bumps in total
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 2000m (0 to 6 560ft)
without any restrictions
2000 to 6000m (6 560 to 20 000ft)
reduce output power or ambient temperature
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating
4W/1000m or 5°C/1000m
> 2000m (6500ft), see Fig. 14-2
Over-voltage category
III
IEC 62103, EN 50178, altitudes up to 2000m
II
altitudes from 2000m to 6000m
Degree of pollution
2
IEC 62103, EN 50178, not conductive
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
**) Do not energize while condensation is present
Fig. 14-1 Output power vs. ambient temp.
Fig. 14-2 Output power vs. altitude
0
-10
0
40
70°C
10
20
30
40
50
60W
60
Ambient Temperature
20
Allowable
Output Power
Output Power
0
0
2000
4000
6000m
10
20
30
40
50
60W
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
Allowable
Output Power
Output Power
15. P
ROTECTION
F
EATURES
Output protection
Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection typ.
31Vdc
max. 32.5Vdc
In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. In such a
case, the output shuts down and stays down until the
input voltage is turned off and on again.
circuit limits the maximum output voltage. In such a
case, the output shuts down and stays down until the
input voltage is turned off and on again.
Output over-current protection electronically
limited
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 2.5mm in diameter
e.g. screws, small parts
Over-temperature protection
not included
Input transient protection
MOV
Metal Oxide Varistor
Internal input fuse
T3.15A H.B.C.
not user replaceable
*) In case of a protection event, audible noise may occur.
Sep. 2010 / Rev. 1.0 DS-ML60.241-EN
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany