Belden 2138A 0101000 Copper Cable - 1000FT Guida Specifiche

Pagina di 3
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CMR, CMX-Outdoor, UL444
EU Directive 2011/65/EU (ROHS II):
Yes
IEEE Specification:
POE per IEEE 802.3af & POE+ per IEEE 802.3at-2009
EU CE Mark:
Yes
EU Directive 2000/53/EC (ELV):
Yes
EU Directive 2002/95/EC (RoHS):
Yes
EU RoHS Compliance Date (mm/dd/yyyy):
01/19/2016
EU Directive 2002/96/EC (WEEE):
Yes
EU Directive 2003/11/EC (BFR):
Yes
CA Prop 65 (CJ for Wire & Cable):
Yes
MII Order #39 (China RoHS):
Yes
Telecommunications Standards:
Category 5e - TIA 568.C.2
ANSI Specification:
ANSI/ICEA S-90-661-2012 Category 5e
Other Specification:
ANSI/ICEA S-56-434 Outdoor Use and ANSI/ICEA S-100-685 Indoor/Outdoor Use
Flame Test
UL Flame Test:
UL1666 Riser
CSA Flame Test:
FT4
Suitability
Suitability - Indoor:
Yes
Suitability - Outdoor:
Yes - CMX - Outdoor
Suitability - Aerial:
Yes - When supported by messenger wire
Suitability - Burial:
No
Suitability - Hazardous Locations:
No
Sunlight Resistance:
Yes
Oil Resistance:
Yes - UL
Non-halogenated:
No
Plenum/Non-Plenum
Plenum (Y/N):
No
Plenum Number:
1533P
Non-Plenum Number:
1533R
Electrical Characteristics (Overall)
Nom. Mutual Capacitance:
Capacitance (pF/ft)
15
Maximum Capacitance Unbalance (pF/100 m):
330
Nominal Velocity of Propagation:
VP (%)
70
Maximum Delay:
Delay (ns/100 m)
538 @ 100MHz
Max. Delay Skew:
Delay Skew (ns/100 m)
45
Maximum Conductor DC Resistance:
DCR @ 20°C (Ohm/100 m)
9.38
Max. Operating Voltage - UL:
Voltage
300 V RMS
 
Page 2 of 3 
08-16-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
2138A  Multi-Conductor - Category 5e Indoor/Outdoor CMR/CMX F/UTP Cable