Sensaphone Model 1800 Manuale Proprietario

Pagina di 142
Sensaphone 1800 Manual
124
APPENDIX F: 1800 Quick Reference Guide
Communications
ID Number 
Identification number of the 1800
 
[SET] or [WHAT IS] + [ID/POWER]
 Range=0–16 
digits, 
Default=blank
ID Message 
Custom message identifying the 1800
 
[SET] or [WHAT IS] + [MESSAGE] + [ID/POWER] 
 Max:6 
seconds 
Default=N/A
 
Zone Message 
Message identifying the zone in alarm
 
[SET] or [WHAT IS] +  [MESSAGE] +  [zone #]
 Max:3.75 
seconds 
Default=N/A
 
Voice Repetitions 
Number of times alarm message is repeated over the phone
  
[SET] or [WHAT IS] + [VOICE REPS] 
 
Min: 1 reps, Max: 10 reps  Default=3 reps
 
Dial-Out Phone Numbers 
Phone numbers dialed to report alarm conditions 
 
[SET] or [WHAT IS] +[PHONE NUMBER] + [number 1–8]
 
 Max: 8 numbers, 48 digits each Default=N/A
 
Call Delay 
Time delay until first call is made 
 
[SET] or [WHAT IS] + [CALL DELAY] (min:sec)
 
Min: 00:00 Max: 60:00  Default=00:30
 
Intercall Time 
Time delay between phone calls 
 
[SET] or [WHAT IS] + [INTERCALL TIME](min:sec) 
 
Min: 00:10, Max: 60:00  Default=01:00 
 
Max Calls 
Number of calls until unit self-acknowledges 
 
[SET] or [WHAT IS] + [MAX CALLS] 
 
Min: 0 calls, Max: 255 calls  Default=100 calls
 
(TAD) Answering Device 
Allows 1800 to bypass answering devices on the same line 
Compatibility 
[SENSOR ON/OFF] + [RINGS/TAD/*] 
 
On or Off,  Default=Off
 
Rings Until Answer 
Number of rings until unit answers an incoming call 
 
[SET] or [WHAT IS] + [RINGS/TAD/*] 
 
Min: 1 ring, Max: 15 rings  DEFAULT=4 rings 
 
 
Speaker Mute 
Turns off the speaker during alarm conditions 
 
[SENSOR ON/OFF] + [MESSAGE/MUTE] 
 
On or Off   Default=Off
 
Call Progress 
Disables call progress detection feature 
 
[SENSOR ON/OFF] + [STATUS/CONFIGURE] 
 
On or Off   Default=On