CHAPTER 6: CONTROLLING THE OUTPUT
The 1800 includes a relay output that can be used to control a light, 
siren, or other device. The output is a Form-C Normally Open/
Normally Closed mechanical relay and is rated for 120VAC 2A. A 
sample wiring diagram is shown below:
H
N
Alarm
Light
OUTPUT
C NO NC
120VAC
Figure 1: Relay output connected to alarm
The output can be programmed to operate in one of 10 automatic 
modes or it can operate in manual mode. The 10
 automatic
 
modes allow the output to automatically turn on and off based 
on individual alarms or any alarm. In
 manual
 mode the output is 
controlled via keypad command or remotely via touch-tone phone 
(See Chapter 8)
. A description of each mode is shown below:
AUTOMATIC MODES
Mode 1
: Output on when zone 1 goes into alarm. Off when alarm 
is acknowledged.
Mode 2
: Output on when zone 2 goes into alarm. Off when alarm 
is acknowledged.
Mode 3
: Output on when zone 3 goes into alarm. Off when alarm 
is acknowledged.
Mode 4
: Output on when zone 4 goes into alarm. Off when alarm 
is acknowledged.
Mode 5
is acknowledged.