Operation 
 
 
 
 
EverGuard Control Panel 
 
51 
 
 
Figure 20: Control Panel Screen 
 2.  To edit a specific parameter, mark the relevant checkbox. The parameter is 
then enabled and you can modify it. 
3.  Under Timer Delay, parameters enable you to set the, configure the 
entry/exit timed devices using the following Timer Delay parameters: 
  Full Entry Timer 
  Full Exit Timer 
  Part Arm Entry Timer 
  Part Arm Exit Timer 
The valid range for each of these parameters is 1 to 180 seconds. 
For compliance with the EN 50131 standard, both Entry and Exit times must be 
set to values of 45 seconds maximum. 
4.  Under Sound, set the sound levels and functions of the alarm for the 
following parameters: 
  Beep Level - The beep level controls the volume of the beep and can be 
set from 1 to 7. 
  Internal Siren Sound Level – The internal siren sound level controls 
the volume of the internal siren and can be set from 1 to 9, or it can be 
set for Progressive (beginning at a lower decibel and escalates). 
  Silent Panic – When Silent Panic is enabled, it is not necessary to set 
the Beep level or the Internal Siren Sound level. 
  Internal Siren Duration – Determines the duration that the internal 
siren sounds. The Internal Siren duration can be set between 5 to 180 
seconds.