2.2 Contact Nipples Designation 
With 4 contact nipples, the PTM 200C offers 2 channels with 4 action states each (upper/lower 
nipple is pressed/released when activating the energy bow). The nipples’ designation is as 
follows: 
 
O
I
B
A
CHANNEL
STATE
O
I
B
A
CHANNEL
STATE
 
Figure 10: Contact nipple designation 
 
 
 
 
Radio signals of the PTM 200C device are event-controlled (energy bow is pressed/released) 
with contact nipple code (channel/state) and unique device identification (fixed 32-bit ID). 
When operating more than one nipple at the same time, note that PTM 200C sends multiple-
button code combinations: 
 
•  N-message: One or two contact nipples have been pressed when activating the 
energy generator Æ Message with nipple code and pressed/released event status of the 
energy bow is sent. 
 
•  U-message: No contact nipple was pressed when activating the energy generator, 
or 3 or 4 nipples have been pressed
 Æ Message with pressed/released event status 
of the energy bow is sent and the information if either none or more than two nipples 
have been pressed. Note that it can’t be differentiated if 3 or if 4 nipples have been 
pressed.  
 
Note: Due to the mechanical hysteresis of the energy bow, in most rocker switch 
device implementations, pressing the rocker sends an N-message and releasing the 
rocker sends a U-message! 
 
 
 
 
 