RadioFrame Networks Inc MCSERIES10 Manuale Utente

Pagina di 152
MC-Series System Installation & Testing 
Scheduled and Unscheduled Maintenance 
94 
RadioFrame Networks, Inc.
 
Index 
Part Number 
Disconnect From 
To 
Type 
DAT_6 
111-0001-02 
BIC:  CRTC 10base2 - ISC 
ISC 1:  10B2-1 
COAX 
CLK_1 
111-0001-02 
BIC:  ERTM 5MHz/1PPS IN 
ISC 1:  SITE REF OUT 1 
COAX 
* Remove both ends of this cable and keep it for the replacement BIC. 
For the AIC, disconnect the following cabling from the rear of the AIC only: 
Index 
Part Number 
Disconnect From 
To 
Type 
P_12 
820-0614-10 
AIC:  power 
PDU:  AIC 
power 
G_13 
820-0609-00 
AIC:  ground 
GND BAR 
ground 
DAT_1 
111-0566-00 
AIC:  ERTM PORT 1 
RBS 1:  10/100 RFN A 
UTP 
DAT_2 
111-0566-00 
AIC:  ERTM PORT 2 
RBS 1:  10/100 RFN B 
UTP 
DAT_3 
111-0566-00 
AIC:  ERTM PORT 3 
RBS 1:  10/100 RFN C 
UTP 
DAT_5 
111-0565-00 
AIC:  ERTM PORT 4 
BIC:  ERTM PORT 2 
UTP 
 
For the RBS 1, disconnect the following cabling from the rear of the RBS 1 only: 
NOTE:  If RBS 2 and RBS 3 are present, refer to the cabling diagrams in Appendix C for 
corresponding cabling indexes. 
Index 
Part Number 
Disconnect From 
To 
Type 
P_6 
820-0616-50 
RBS 1:  power 
PDU:  RBS 1 
power 
G_8 
820-0609-00 
RBS 1:  ground 
GND BAR 
ground 
RF_1 
820-0611-20 
RBS 1:  Tx A 
RF Shelf 1:  Tx IN A  
RF cable
 
RF_4 
820-0611-20 
RBS 1:  Rx A 
RF Shelf 1:  Rx OUT A  
RF cable
 
AL_1 
820-0607-00 
RBS:  ALARM INPUT A 
RF Shelf 1:  ALARM 
serial 
DAT_1 
111-0566-00 
RBS 1:  10/100 RFN A 
AIC:  ERTM PORT 1 
UTP 
RF_2 
820-0611-20 
RBS 1:  Tx B 
RF Shelf 2:  Tx IN B  
RF cable
 
RF_5 
820-0611-20 
RBS 1:  Rx B 
RF Shelf 2:  Rx OUT B  
RF cable
 
AL_2 
820-0607-00 
RBS:  ALARM INPUT B 
RF Shelf 2:  ALARM 
serial 
DAT_2 
111-0566-00 
RBS 1:  10/100 RFN B 
AIC:  ERTM PORT 2 
UTP 
RF_3 
820-0611-20 
RBS 1:  Tx C 
RF Shelf 3:  Tx IN C  
RF cable
 
RF_6 
820-0611-20 
RBS 1:  Rx C 
RF Shelf 3:  Rx OUT C  
RF cable
 
AL_3 
820-0607-00 
RBS:  ALARM INPUT C 
RF Shelf 3:  ALARM 
serial 
DAT_3 
111-0566-00 
RBS 1:  10/100 RFN C 
AIC:  ERTM PORT 3 
UTP 
 
Remove the chassis from the rack, and package it for shipment.  
24 
Mount the replacement chassis.  
While supporting the chassis, slide the chassis into the cabinet mounting position. Secure the 
chassis to the cabinet mounting rails using the four mounting screws provided with the unit. 
Tighten the screws to 4.5 Nm (40 in-lb).  
35 
Reconnect the cabling to the replacement chassis as defined in Step 2.  
Use the SMA torque wrench for all SMA connectors. 
Using the breakers on the PDU, turn up the BICAIC, and RBS 1 (and RBS 2 and RBS 3 if 
present), and then verify that the components are operational before proceeding.