KROHNE FMCW10G52 Manuale Utente
03/2012 - 4001904901 - HB OPTIWAVE 5200 R01 en
www.krohne.com
47
OPTIWAVE 5200 C/F
OPERATION
6
Measurement type definitions
Measurement type
Description
Available units
LEVEL
This is a display and an output function option. It is
the height from the bottom of the tank to the surface
of the liquid (Tank height - Distance).
m, cm, mm, in (inches), ft
(feet)
DISTANCE
This is a display and an output function option.
It is the distance from the face of the flange to
the surface of the liquid.
m, cm, mm, in (inches), ft
(feet)
CONVERSION
This is a display and an output function option. It
gives the volume, mass or flow rate of the tank
contents. This data is available if you prepare a
volume, mass or flow rate table in configuration
mode. For
data on how to prepare the conversion table,
refer to
How to configure the device to
measure volume or mass
on page 68.
m3, L, gal (US gallons), ImpG (Imperial
gallons), ft3, bbl (oil barrel), kg, t, Ston,
Lton, m, cm, mm, in, ft, m3/h, ft3/h
ULLAGE CONV.
This is a display and an output function option. It
gives the empty volume or remaining mass that
can be put in the tank. This data is available if you
prepare a volume or mass table in configuration
mode. For data on how to prepare the conversion
table, refer to
How to configure the device to
measure volume or mass
on page 68.
m3, L, gal (US gallons), ImpG (Imperial
gallons), ft3, bbl (oil barrel), kg, t, Ston,
Lton, m, cm, mm, in, ft, m3/h, ft3/h
OUTPUT I (mA)
The current output of the device.
mA
OUTPUT I (%)
The percentage of the current output. 0% = 4
mA. 100% = 20 mA.
%
6.3 Configuration mode
6.3.1 General notes
Change the settings of your device in Configuration mode. Data about the menus is given on page
58. You can:
58. You can:
• Use the 1.0.0 INFORMATION menu to read settings, device software versions and error records. For more data about the
Information menu, refer to Table A. Info.
• Use the 2.0.0 SUPERVISOR menu run diagnostic tests, set up a conversion table for volume, mass or flow rate measurement,
change critical parameters for difficult process conditions, reset the device and change basic parameters (tank height etc.),
output settings, HART Address etc. For more data about the Supervisor menu, refer to Table 2. Supervisor.
output settings, HART Address etc. For more data about the Supervisor menu, refer to Table 2. Supervisor.
INFORMATION!
It is not possible to enter the 3.0.0 SERVICE and 4.0.0 MASTER menus. These menus are for
factory calibration and qualified service personnel only.