InfoProx Entry   
 
Configuring the Door Control Unit 
08:00 to 17:00, personnel who know the GIN are allowed access during 
these hours, but after the Time Zone expires, entrance is allowed only 
to cardholders. The default GIN is 1234. 
·  Set Scode:  Set Site Code. If the site code is entered into the InfoProx 
door control unit, then all cards read by the unit must have this site 
code to be valid and to enable access. 
 
If no site code is configured during setup, the unit will allow any card, 
regardless of the site code, to be added and used to enable access. 
However, this condition may not provide the degree of security desired.  
 
 
By default, the site code is set to –1. If the site code is set to 
0 by the user, it will revert to the default or –1. This default 
allows any added card to be used as valid. 
If the site code is enabled after cards are entered, the unit 
will check the validity of all cards in the unit’s database and 
match to the site code.  If the previously entered cards have 
no site code or have site codes that do not match, then the 
cards will be invalid and will not work to enable access. 
 
To preview the modes, users should view the Configuration screens by pressing 
#. After previewing the Set Scode screen, pressing will return users to the 
Administration menu, where they can again enter 3-Config to start the 
configuration process. 
Before you begin configuring 
The following list prepares you for the material you will need for the setup 
process. 
·  Current time, including day, month, and year 
·  If the optional time zone setup is desired, decide on a time zone time 
parameter and who will be given access. You can have only one time 
zone per door control unit. If no time zone is setup, then access will be 
on a 24-hour clock and accessible with a valid card and PIN associated 
with the card. If there is no PIN associated with the card, then access 
will be allowed by presenting just the card, assuming that it is a valid 
card in the database. 
·  Determine if the factory defaults are adequate for door strike time and 
door close time.  If not, determine an appropriate time for the setup. 
·  If you are going to use a Global Identification Number (GIN) with a 
number other than the default of 1234, use a 4-digit GIN. 
·  Optional site code 