System Commissioning Guide 
4 Troubleshooting
 
Issue 02 (2006-10-10) 
Huawei Technologies Proprietary 
4-3
 
To Handle 
Take the Following Action 
Power supply alarms, such as high 
voltage alarms, low voltage alarms, 
power failure alarms, and power fan 
failure alarms 
Check that: 
The PSU works normally. 
The mains supply is normal. 
Board environment alarms such as 
board temperature alarms 
Check that: 
The board is normal. 
Environmental conditions are normal. 
Other alarms, such as the alarms caused 
by board hardware faults and software 
operation errors 
Handle according to the suggestions provided 
by the system. 
 
4.3 Room Environment Alarms 
This section describes the alarms related to the BTS3606E equipment room environment and 
their handing methods. 
4.3.1 Alarm Description 
Room environment alarms are collected by an environment alarm chest (EAC) connected 
with the BTS3606E. Such alarms include the fire alarm, smoke alarm, access control alarm, 
water alarm, temperature alarm, humidity alarm, and air-conditioner alarm. 
4.3.2 Alarm Handling 
The process for handling an environment alarm is as follows: 
Step 1  Upon receiving an environment alarm, the OMU starts the related external devices, such as 
air-conditioners, fire extinguishers, smoke removers, and dehumidifiers. 
Step 2  The OMU reports alarm messages to the OMC. 
Step 3  The OMC displays the alarm on terminals so that maintenance engineers can take actions to 
clear the alarms. 
----End