LONWORKS( Data Cables 
•  The FTT10A Echelon
 v1.2 User Guide recommends the cables indicated 
in Table 2. 
Manufacturer and 
model 
AWG Connection 
to 
bus 
-
maximum total length 
[m] 
Connection in free topology 
–maximum node-node 
length max. [m] 
Belden 85102 
16 
2700 
500 
Belden 8471 
16 
2700 
400 
Level IV (twisted pair, 
typically solid and 
unshielded) 
22 1400 
400 
JY (St) 2x2x0.8 (4-
wire helical twist, 
solid shielded) 
20 900 
320 
Table 2: Recommended L