Honeywell International Inc. RTU-L12 Manuale Utente

Pagina di 22
 
1.5.4 Input Cable 2 – Push Button 
Supervised input 2 is for the push button status; resistors must be installed 
at the door push button contacts. 
Wh
it
e
Yel
lo
w
bu
tt
on
 con
tac
t
NO
 CO
NT
ACT
 
 
IN2 (orange) 
GND 
Figure 9: Supervised Input 2 connection– Push button 
 
Yellow resistor: 1210 Ohm 1% 
White resistor: 392 Ohm 1% 
Push button close resistance: 296 Ohm 
Push button open resistance: 1210 Ohm  (normality) 
Max wires resistance: 25 Ohm  
 
Note: in case the push button is unused the INPUT has to be 
terminated with the Yellow resistor. 
 