1.5.5 Output Cable Relay 1- Door Open  
The Relay 1 output is used for door control. It makes both NO and NC 
contacts available. 
The external load can be powered directly by AC or DC, in accordance 
with the following limits:  
Minimum Load:  12VDC / 10mA 
Voltage  
Working Current Peak Current  
max 0.5 Sec 
(inductive load) 
Suppressor 
12VDC 3A 
10A 
1N4004 
Diode 
 
30VDC 2A 
10A 
1N4004 
Diode 
 
42VDC 0.5A 
7A 
1N4004 
Diode 
 
42VAC 0.5A 
7A 
MOV 
75Vrms 
 
•  Inductive load with direct current: 
In this case it is mandatory to use the 1N4004 diode, which is provided, 
(or an equivalent) in parallel to the coil of the electrical locking device, to 
increase the life of the relay inside the RTU – see Figure 9
•  Inductive load with alternating current: 
In this case it is mandatory to use the MOV (75VAC), which is provided, 
(or an equivalante) in parallel to the coil of the electrical locking device, 
to increase the life of the relay inside the RTU 
− see Figure 10. 
•  Life: assuming the relay is activated 200 times a day and that the 
voltage/current limits of the preceding table are respected, the life is 
guaranteed for at least 6 years; if the relay is activated less frequently, 
the life of the relay increases proportionally.  
In case of excessive use (> 200 operations / day) it is suggested to use 
an external relay. 