1.5.6 Output Cable Relay 2 – Signal Light  
Output Relay 2 is used for signaling the status of the door (gateway 
occupied / free ) and provides both NO and NC contacts. 
The external load can be powered directly from AC or DC power, in 
accordance with the following limits:  
 
Voltage  
Working Current 
Peak Current (max 
0.5 Sec) 
Suppressor 
30VDC 
0.5 A 
2 A 
1N4004 Diode 
30VAC 
0.5 A 
2 A 
MOV 75Vrms 
 
•  Inductive load with direct current: 
In this case, it is mandatory to use a repeater relay and a 1N4004 diode 
in parallel to the coil for the electrical locking device in order to increase 
the life of the relay inside the RTU 
− see Figure 12. 
•  Inductive load with alternating current: 
In this case, it is mandatory to use a repeater relay and the MOV 
(75VAC) in parallel to the coil for the electrical locking device in order to 
increase the life of the relay inside the RTU see Figure 13. 
•  Life: assuming the relay is activated 200 times a day and that the 
voltage/current limits of the preceding table are respected, the life is 
guaranteed for at least 6 years; if the relay is activated less frequently, 
the life of the relay increases proportionally.  
•  In case of excessive use (> 200 operations / day) it is suggested to use 
an external relay. 