The controller circuit has clock oscillators at 32 kHz. , 500kHz. and 8 MHz.  These 
frequencies and related harmonics were also investigated.  Two frequencies related to 
the 8 MHz. clock (32.00 MHz. and 40.00 MHz.) were detected but were greater than 
30dB below the limit and are not recorded in the table.         
 
At each detected emission frequency, the device was measured by rotating the 
turntable and adjusting the antenna height over a range of 1 to 4 meters to obtain the 
maximum output level.  This procedure was performed with both horizontal and vertical 
antenna polarizations for both of the setup positions shown in the test setup photos.  
The peak reading for each frequency was recorded in the fourth column in Table 1 
below. 
 
CLIENT:   HONEYWELL
FCC ID:  HS9-T8665C
EUT:  DATA TRANSMITTER
PART 15.249
TEST DATE:  05-DEC-01
Ant. 
Polar. 
H/V
916.431
V
30.5
-44.14
46559
50000
1832.862
V
30.2
-91.17
200
500
2749.293
V
33.4
-93.66
217
500
3665.724
H
35.7
-97.21
188
500
4582.155
V
36.6
-100.83
138
500
5498.586
H
38.6
-104.54
113
500
6415.016
H
39.1
-111.06
56
500
7331.446
V
40.8
-117.52
33
500
Table 1
RADIATED EMISSIONS DATA
Frequency 
In          
MHz.
Peak 
Power 
uV/m@3m
Peak 
reading 
dBm
Ant. 
Factor 
dB
ANTENNA:  DIPOLES/DRG HORN
Duty 
Cycle    
-dB
FCC      
Limit 
uV/m@3m
Corrected 
Power 
uV/m@3m
 
 
 
Measurements taken for weak emissions were performed by reducing the distance from 
the measurement antenna to 1 meter and factoring –9.54dB into the calculation.  This 
method was used for the 7
th
 and 8
th
 harmonics. 
 
 
C. OCCUPIED BANDWIDTH AND DUTY CYCLE 
 
The occupied bandwidth measurement was made using an HP8596E spectrum 
analyzer and plotted with an HP7475A pen plotter.  The duty cycle correction factor for 
this device is approximately –4dB, but since the peak readings for all detected 
harmonics were below the limits, the duty cycle correction factor was not applied to the 
calculations.