Installation Guide
69-2537EFS—01 4
1H/1C Heat Pump (no auxiliary heat)
Rc 
Power 
[1]
[R+Rc joined by jumper]
O/B  Changeover valve 
[5]
Compressor relay
Fan relay
24VAC common
[3]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
2H/1C Heat Pump (with auxiliary heat)
Equipment monitor 
[6, 7]
Aux/E Auxiliary heat relay (Heat 2) 
[8]
Rc 
Power 
[1]
[R+Rc joined by jumper]
O/B  Changeover valve 
[5]
Compressor relay
Fan relay
24VAC common
[3]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
2H/2C Heat Pump (no auxiliary heat)
Y2 
Compressor 2 relay
Rc 
Power 
[1]
[R+Rc joined by jumper]
O/B  Changeover valve 
[5]
Compressor 1 relay
Fan relay
24VAC common
[3]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
3H/2C Heat Pump (with auxiliary heat)
Y2 
Compressor 2 relay
Equipment Monitor 
[6, 7]
Aux/E Auxillary heat relay (Heat 2) 
[8]
Rc 
Power
[R+Rc joined by jumper]
O/B  Changeover value 
[5]
Compressor 1 relay
Fan relay
24VAC common
[3]
  
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
Wiring
See [
notes
] below
 [1] 
Power supply. Provide disconnect means and overload protection as required.
 [3] 
Connection to 24VAC common at the transformer is required.
 [5]
O/B set to control as either O or B in installer setup.
 [6]
If L terminal is used, 24VAC common (terminal C) must be connected.
 [7]
Heat pump reset (powered continuously when thermostat is set to Em. Heat mode; system monitor when 
set to Heat, Cool, or OFF).
 [9]
See page 14 for more details.
Terminal Designations
 
Conventional Terminal Letters:
Heating power. Connect to secondary side 
of heating system transformer.
Rc 
Cooling power. Connect to secondary side 
of cooling system transformer.
Common wire from secondary side of
cooling transformer (if 2 transformers).
1st stage heat relay.
W2 
2nd stage heat relay.
1st stage compressor contactor.
Y2 
2nd stage compressor contactor.
Fan relay.
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
Heat Pump Terminal Letters:
Heating power. Connect to secondary side 
of heating system transformer.
Rc 
Cooling power. Connect to secondary side 
of cooling system transformer.
Common wire from secondary side of
cooling system transformer.
1st stage compressor contactor.
Y2 
2nd stage compressor contactor.
Aux/E Auxiliary heat relay.
Fan relay.
Heat pump reset (powered continuously 
when System is set to Em Heat; system 
monitor when set to Heat, Cool or Off).
O/B  Changeover valve for heat pumps.
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
Wiring guide—heat pump systems