20
69-2688—01 I/O-CHTSTAT03
Heat pump with outdoor temperature lockouts
Outdoor temperature lockouts are optional. See Installer Setup
options (ISU 3120).
options (ISU 3120).
Heat pump only
Heat pump with backup heat as needed *
Backup heat only
Heat pump only
Heat pump or backup heat operates *
Backup heat only
Outdoor temperature
Outdoor temperature
Backup heat lockout
Backup heat lockout
Compressor lockout
Compressor lockout
*
No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat
Upstage Timer expires.
Upstage Timer expires.
Heat pump stays ON when backup heat turns on.
*
No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup
Heat Upstage Timer expires.
Heat Upstage Timer expires.
Heat pump turns OFF when backup heat turns on.
Electric - Backup heat allowed to run with heat pump
Fossil Fuel - Backup heat NOT allowed to run with heat pump