Wiring
Once the GP-IO-332 is mounted, connect the power.
 
Fig. 2  Wiring diagram.
Connecting power
Connect the GP-IO-332 to 24VAC power from a UL 
Listed Class-2 24VAC transformer (not included). You 
can use the same transformer for the GP-HUB-100 and 
other associated controller(s) as long as the total load 
does not exceed 100VA and all devices are half-wave. 
The GP-IO-332 is a half-wave device.
CAUTION! Half-wave devices and full-wave devices must not
use the same AC transformer. You must maintain wiring
polarity. Failure to do so can result in equipment damage.
ATTENTION! Les dispositifs demi-onde et les dispositifs à
onde pleine ne doivent pas utiliser le même transformateur AC.
Le défaut de maintient de la polarité du câblage peut
endommager l'équipement.
USB Power
The GP-IO-332 can also be powered from a USB cable 
that provides 5VDC power. Some USB ports can supply 
sufficient power and some can not. Review the user 
documentation for the power source to determine 
whether the USB port supplies sufficient power.
DIP Switches
The GP-IO-332 has two banks of DIP switches. The first, 
6-position switch, sets the network address for the 
wireless network (must match GP-HUB-100). The 
second, 8-position switch, is used to set the Remote 
Device address (0-99) that the device will use when 
connecting to the Hub.
The RSSI LEDs also flash to indicate error conditions.
Fig. 3  Locations of GP-IO-332 components.
XX
XX
XXX
XXXXXXX
GND
COM
24V
AC
MSTP-
POWER
MSTP+
XFMR
24VAC
O/P
FUSED AC 
SOURCE
PANEL GROUND
Table 1  RSSI Error Conditions
Flash Pattern
Status
One red
No communication or the device has not 
joined the wireless network
One yellow and two 
green
Wireless network MAC address does not 
match device type
Two green
Multiple devices have identical wireless 
network MAC addresses
One red and one green Lost communication with GP-HUB-100. 
Working to re-establish connection.
One flashing red and 
two solid green
Device initialization in progress
BO LED
AC POWER
TERMINALS
USB 
TERMINALS
AI TERMINALS
BO TERMINALS AO TERMINALS