2 Planning and Preparation 
2.1  Installation Planning 
It is important to ensure proper planning and site preparation is complete prior to 
beginning the installation of the MCPS2135.  The following sections describe 
installation considerations and the information required before beginning the 
installation procedure.  Spectrian Applications Engineering is always available to 
assist with planning for the installation of the MCPS2135. 
1.22.2 
Site Planning Guide 
For each MCPS2135 cell site installation, there must be a Site Planning or Site 
Engineering guide giving the detailed information on the site considerations, rack 
installation, cable connections, and Radio Parameters. 
Note:  Local building  and fire codes govern the manner in which some site 
preparation and installation tasks are performed.  Spectrian recommends that 
you consult your local building inspector or a licensed engineer to ensure that 
the site installation conforms to local building codes. 
2.2.1 Site Considerations 
Intended Installations 
The MCPS2135 system is intended for installation only in restricted access areas 
(dedicated equipment rooms, equipment closets, environmental shelters, or the 
like) in accordance with Articles 110-16, -17, and -18 of the National Electrical 
Code, ANSI/NFPA No. 70. 
Weight 
The MCPS2135 shelf and each RF module weigh approximately 50 pounds (22.7 
kg); the fully equipped system weighs 250 pounds (113.3 kg).  The system must 
be installed, using the appropriate mounting kit, into a rack capable of supporting 
the unit, and located on a floor or surface capable of supporting the combined 
weight of the rack, the MCPS2135, and the installer or technician. 
Floor Covering 
If you intend to use a floor covering under the MCPS2135, avoid combustible 
materials , industrial carpeting, and materials that will permit generation of 
electrostatic charges. 
Illumination 
The MCPS2135 is designed to be installed and serviced under normal workroom 
lighting.  During installation, room lighting must be bright enough to allow 
reading instructions and inspection of modules, but not so bright as to interfere