Lutron Electronics Company Inc 0092 Manuale Utente

Pagina di 2
Installation
WARNING – Shock Hazard – To avoid the risk of electric shock locate and remove fuse or 
lock circuit breaker in the OFF position before proceeding. Wiring with power ON could result in 
serious injury or death.
1.  Turn power OFF at fusebox or circuit breaker.
2.  Check the installation for short circuits before installing control(s). With power OFF, install standard 
mechanical switch(es) between Hot and load. Restore power. If lights or fans do not work or a breaker 
trips, check wiring. Correct wiring and check again. Install control(s) only when short is no longer 
present. Warranty is void if control is turned ON with a shorted circuit.
3.  Verify power is off and wire controls according to one of the following options:
  a.  Terminals: Trim or strip wallbox wires to the length indicated by the strip gauge on the 
back of the control.
•  Push-In Terminals: Use with 14 AWG (1.5 mm
2
solid copper wire only. Do NOT use 
stranded or twisted wire. 
Insert wires fully. To release wire, insert small, flat screwdriver into slot below push-in 
terminal. Push screwdriver in while pulling wire out. 
 OR
•  Screw Terminals: Use with 12 AWG (2.5 mm
2
) or 14 AWG (1.5 mm
2
solid copper wire 
only. Do NOT use stranded or twisted wire.
Wrap wire around screw terminal. Tighten securely to 5 in-lb (0.55 N
m).
  b.  Wire Connectors: Prepare wires. When making wire connections, follow the 
recommended strip lengths and combinations for the supplied wire connector.
 
NOTE: Wire connectors provided are suitable for copper wire only.
  Wire Connector:
•  Strip insulation 3/8 in (10 mm) for 14 AWG (1.5 mm
2
) or 12 AWG (2.5 mm
2
) wire.
•  Strip insulation 7/16 in (11 mm) for 18 AWG (0.75 mm
2
) or 16 AWG (1.0 mm
2
) wire.
•  Use to join one or two 14 AWG (1.5 mm
2
) or 12 AWG
 
 (2.5 mm
2
) wires with one 18 AWG (0.75 mm
2
) or 
16 AWG (1.0 mm
2
) wire.
Dimming Range Adjustment (Dimmer Only)
If dimming range of your lamps is satisfactory, save these instructions for future reference, otherwise go 
to to step 1 below.
1. Hold the tapswitch and the lower rocker until a status LED blinks, indicating current low end level.
2.  Hold the lower rocker until the bottom status LED is reached. Hold the raise rocker until all lamps are on 
and stable (no flickering). Single tap the tapswitch to save setting.
3.  Single tap the tapswitch to turn off bulbs. Single tap the tapswitch again. If all lamps do not turn on or 
are not stable, repeat step 1, and in step 2 increase light with the raise rocker.
Installation Instructions
Please Read Before Installing
Troubleshooting Guide
Lutron Electronics Co., Inc. 
7200 Suter Road  |  Coopersburg, PA 18036-1299
P/N 044326   Rev. A   04/2013
Important Notes
WARNING – Entrapment Hazard – To avoid the risk of entrapment, serious injury, or death, these 
controls must not be used to control equipment which is not visible from every control location or 
which could create hazardous situations such as entrapment if operated accidentally. Examples of 
such equipment which must not be operated by these controls include (but are not limited to) motorized 
gates, garage doors, industrial doors, microwave ovens, heating pads, etc. It is the installer’s responsibility 
to ensure that the equipment being controlled is visible from every control location and that only suitable 
equipment is connected to these controls. Failure to do so could result in serious injury or death.
Codes: Install in accordance with all local and national electrical codes.
Grounding: When no “grounding means” exist in wallbox, the 2011 National Electrical CodeR (NECR) 
allows a control to be installed as a replacement if 1) a nonmetallic, noncombustible faceplate is used with 
nonmetallic attachment screws or 2) the circuit is protected by a ground fault circuit interrupter (GFCI). 
When installing a control according to these methods, cap or remove green wire before screwing control 
into wallbox. 
Environment: Ambient operating temperature: 32 °F to 104 °F (0 °C to 40 °C), 0% to 90% humidity, non-
condensing. Indoor use only.
Spacing: If mounting one control above another, leave at least 4 ½ in (114 mm) vertical space between 
them.
Wallplates: LutronR ClaroR and Satin ColorsR wallplates are recommended for best color match and 
aesthetic appearance. Do not paint controls or wallplates.
Cleaning: To clean, wipe with a clean damp cloth. DO NOT use any chemical cleaning solutions.
Wallboxes: Lutron recommends using 3 ½ in (89 mm) deep wallboxes for easier installation. Several 
controls may be installed in one multigang wallbox. See 
Derating Chart.
Remote Dimmers: Use only remote dimmers with dimmers. Up to 9 remote dimmers may be used. 
Mechanical 3- or 4-way switches will not work.
RF Device Placement: RF dimmers must be located within 30 ft (9 m) of an RF signal repeater. Remote 
dimmers are not required to be within a specific range of a repeater.
For systems with an RF signal repeater, RF dimmers cannot be controlled by the system until they are 
programmed in a system according to the system Setup Guide.
English
Lutron, Claro, Satin Colors, Maestro, RadioRA, and ) are registered trademarks and RadioRA 2 and FASS are trademarks of Lutron Electronics Co., Inc. 
NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.  
©2013 Lutron Electronics Co., Inc.
Technical Assistance:
U.S.A. / Canada:  1.800.523.9466
Mexico: +1.888.235.2910
Brazil: +55 (11) 3257-6745 (M-F 8:30 to 17:30 BRT)
Other Countries: +1.610.282.3800 
24 hours a day, 7 days a week
www.lutron.com
* Typical Power Consumption: 
  Dimmer: 0.6 W (load is off, nightlight mode enabled)
  Remote Dimmer: 0 W (load is off)
For system Setup Guide and tools visit www.lutron.com/radiora2
 When using controls in single location installations, tighten the blue terminal without any wires 
attached. DO NOT connect the blue terminal to any other wiring or to ground.
 Dimmer may be installed in any location in the circuit.
 Install only 1 dimmer per circuit. Up to 9 remote dimmers may be connected to a dimmer. Total blue 
terminal wire length may be up to 250 ft (76 m).
Lamp Replacement
WARNING – Shock Hazard – For any procedure other than routine lamp replacement, power 
must be disconnected at the main electrical panel. Working with power ON could result in 
serious injury or death.
For your safety during routine lamp replacement, remove power from the fixture(s) by moving the 
FASS
 switch into the OFF position on the dimmer and all remote dimmers.
Symptom
Probable Cause and Action
Light doesn’t turn ON / OFF 
when tapswitch on dimmer 
or remote dimmer is 
pressed
Power not present
   •  Circuit breaker OFF or tripped. Perform short circuit check.
   •  FASS™ is in the OFF position. Move FASS™ to the ON position. 
Check the dimmer and all of the remote dimmers. See 
Lamp 
Replacement.
Wiring
   •  Wires shorted. Make sure the blue terminal is not grounded or 
shorted to any other wires.
   •  Wiring error. Check wiring to be sure it agrees with installation 
instructions and wiring diagrams.
Load is less than minimum load requirement
   •  Make sure the connected load meets the appropriate minimum load 
requirement for that control. See 
Load Specifications.
Lamps burned out or not installed
   •  Replace or install lamps.
Dioded lamps
   •  If dioded lamps are being used, replace with non-dioded lamps.
Light turns ON and OFF 
continuously or lights turn 
ON when tapswitch is 
pressed, then turn OFF
Load does not meet the minimum load requirement
   •  Increase load to meet the appropriate minimum load requirement for 
that control. See 
Load Specifications.
Lights turn off while being 
dimmed
Lamps are not dimmable or low end is not adjusted properly
   •  Verify lamps are rated as dimmable and on the compatible list  
(www.lutron.com/dimcfl led).
   • Complete the steps in 
Dimming Range Adjustment.
Lights turn on at high light 
level but do not turn on at 
low light level
Lights flicker or flash when 
dimmed to a low light level
Lights don’t turn ON/OFF 
from a keypad
Improper programming
   •  Program according to the system Setup Guide.
Out of RF range
   •  Reposition to be within 30 ft (9 m) of an RF signal repeater.
Wiring
   •  Wires shorted. Make sure the blue terminal is not grounded or 
shorted to any other wires.
   •  Wiring error. Check wiring to be sure it agrees with installation 
instructions and wiring diagrams.
Wallplate is warm
Solid-state control dissipation
   •  Solid-state dimmers internally dissipate about 2% of the total 
connected load. It is normal for dimmers to feel warm to the touch 
during operation.
NOTE: Refer to the system Setup Guide for additional troubleshooting suggestions.
Status LEDs (Dimmer only)
Indicate light level; glows softly 
as night light when load is off
Tapswitch
Tap on/off
Dimming Rocker
Press to Brighten
Press to Dim
FASS
TM
Front
Accessible
Service
Switch
Dimmer Operation
Return to Factory Settings
NOTE: Returning a dimmer to the factory settings will remove it from the system and erase all 
programming.
Step 1 :  Triple tap the tapswitch on a control. DO NOT release after the third tap.
Step 2 :  Keep the tapswitch pressed on the third tap (for approximately 3 seconds) until the LEDs on the 
dimmer start to scroll up and down quickly, or the LED on the switch flashes quickly
Step 3 :  Release the tapswitch and immediately triple tap the tapswitch again. The LEDs on the dimmer will 
scroll up and down slowly. The LED on the switch will flash slowly.
The control has now been returned to factory settings and needs to be reprogrammed into a system.
Designer-Style RF MaestroR
*   Dimmer: 
RRD-6CL (120 V~    50 / 60 Hz)
*  Remote Dimmer: 
RD-RD (120 V~    50 / 60 Hz)
Dimmer
Remote 
Dimmer
Single Location Installation
1
Wiring Diagram 1
Green
Ground
Hot/Live
Neutral
Load
Dimmer
120 V~  
50/60 Hz
Blue
1
Brass
Black
Multi-Location Installation
2, 3
Brass
Black
Blue
Green
Ground
Load
 
Dimmer / Remote Dimmer
2
Brass
Black
Blue
Green
Ground
Remote Dimmer / Dimmer
2
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Remote Dimmer / Dimmer
2
120 V~  
50/60 Hz
Wiring Diagram 2
FCC/ IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). 
Operation is subject to the following two conditions: (1) This device may not cause interference, and (2) 
this device must accept any interference, including interference that may cause undesired operation. 
Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to 
operate this equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, 
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against 
harmful interference in a residential installation. This equipment generates, uses and can radiate radio 
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful 
interference to radio communications. However, there is no guarantee that interference will not occur in a 
particular installation. If this equipment does cause harmful interference to radio or television reception, 
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the 
interference by one or more of the following measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
— Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help.
Warranty
For warranty information, please visit www.lutron.com/TechnicalDocumentLibrary/Warranty.pdf
P/N 044326 
Rev. A
1  Dimmer Load Type: Designed for use with permanently installed incandescent, tungsten halogen, CFL, 
or LED loads only. Do not install dimmers to control receptacles, MLV loads, ELV loads, or motor-operated 
appliances. For information on controlling additional load types, please visit www.lutron.com
2  Remote Dimmer: Designed for use with 120 V~ dimmers.
Twist wire 
connector tight.
  For single and multi-location installations see 
Wiring Diagrams.
Mounting Diagram
Control 
Mounting 
Screws
Wallbox
Control
Included:
Wire Connector (1)
Mounting Screws (2)
Adapter 
Mounting 
Screws
Wallplate adapter and 
wallplate purchased 
separately.
Wallplate 
Adapter
Wallplate
  Multigang Installations
  In multigang installations, several controls are grouped horizontally in one multigang wallbox. When 
combining dimmers in a wallbox, derating is required; however, no derating is required for remote 
dimmers. 
  Mixing lamp types (using a combination of CFL/LED, and Incandescent/Halogen bulbs) and removal of 
Dimmer side sections may reduce maximum wattage as shown in the chart below.
  Derating Chart
CFL/LED 
Total Wattage
Incandescent/Halogen Total Wattage
0 W
+
50 W – 600 W
50 W – 500 W
50 W – 400 W
1 W – 25 W
+
0 W – 500 W
0 W – 400 W
0 W – 300 W
26 W – 50 W
+
0 W – 400 W
0 W – 300 W
0 W – 200 W
51 W – 75 W
+
0 W – 300 W
0 W – 200 W
0 W – 100 W
76 W – 100 W
+
0 W – 200 W
0 W – 100 W
0 W – 50 W
101 W – 125 W
+
0 W – 100 W
0 W – 50 W
0 W
126 W – 150 W
+
0 W
0 W
0 W
Example
 If side sections from one side of dimmer are removed and you have two 24 W CFL bulbs installed (Total CFL Wattage = 48 W), 
you may add up to 300 W of incandescent or halogen lighting.
A
B
C
B
B
B
C
B
A
Load Specifications
Control
Load Type
Minimum Load
Maximum Load
-6CL
1
Incandescent/Halogen
50 W
600 W
CFL/LED
0 W
150 W
-RD
2
See Dimmer
8.3 A
4.  Push all wires back into the wallbox and loosely fasten the control to the wallbox 
using the control mounting screws provided. Do not pinch the wires.
5.  Attach the Lutron
®
 Claro
®
 or Satin Colors
®
 wallplate adapter and wallplate. See 
Mounting Diagram.
  a.  Install wallplate adapter onto front of control(s).
  b.  Tighten control mounting screws until wallplate adapter is flush to wall (do not over-tighten).
  c.  Snap wallplate onto wallplate adapter, and verify that control is aligned properly.
  d.  If controls are misaligned, loosen mounting screws appropriately. 
6.  Restore power. Verify correct local operation. See Dimmer Operation.
NOTE: When using CFLs or LEDs with this dimmer, only bulbs marked 
or rated as DIMMABLE and on the compatible list can be used. 
For a complete list of compatible DIMMABLE CFLs and LEDs please visit 
www.lutron.com/dimcflled