Lutron Electronics Company Inc 0096 Manuale Utente

Pagina di 1
        
 
Lutron Electronics Co., Inc. | 7200 Suter Road 
Coopersburg, PA 18036-1299, U.S.A.
RF Relay Module | Installation
with SoftswitchR
041423 
Rev. A
08/2013
  Important Notes:
 
•  
For installation by a qualified electrician in accordance 
with all local and national electrical codes. 
• Note: Use copper conductors only.
•  Check to see that the device type and rating is suitable  
for the application.
•  DO NOT install if product has any visible damage.
•   If moisture or condensation is evident, allow the product 
to dry completely before installation.
•  Operate between 32 °F to 131 °F (0 °C to 55 °C).
•  0% to 90% humidity, non-condensing.
•  For indoor use only. 
 
Please read before installing
LMJ-16R-DV-B
120 / 277 V~  50 / 60 Hz  16 A  
1/2 HP at 120 V~         1
1
2
 HP at 277 V~
UL 2043 Plenum Rated
LMK-16R-DV-B
LMN-16R-DV-B
LMM-16R-DV-B
LMQ-16R-DV-B
220  - 240 V~  50 / 60 Hz  16 A  
6 A Motor (LMK- Model)
FCC Information: 
(LMJ- model only)
This device complies with part 15 of the FCC Rules and 
Industry Canada license-exempt RSS standard(s). Operation is 
subject to the following two conditions:
(1) This device may not cause interference, and
(2)  this device must accept any interference, including 
interference that may cause undesired operation.
Modifications not expressly approved by Lutron Electronics Co., 
Inc. could void the user’s authority to operate this equipment. 
NOTE: This equipment has been tested and found to comply 
with the limits for a Class B digital device, pursuant to part 
15 of the FCC Rules. These limits are designed to provide 
reasonable protection against harmful interference in a residential 
installation. This equipment generates, uses and can radiate radio 
frequency energy and, if not installed and used in accordance 
with the instructions, may cause harmful interference to radio 
communications. However, there is no guarantee that interference 
will not occur in a particular installation. If this equipment does 
cause harmful interference to radio or television reception, which 
can be determined by turning the equipment off and on, the 
user is encouraged to try to correct the interference by one or 
more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
•  Connect the equipment into an outlet on a circuit different from 
that to which the receiver is connected.
Warranty: 
For warranty information, please visit 
www.lutron.com/TechnicalDocumentLibrary/Warranty.pdf
www.lutron.com/TechnicalDocumentLibrary/Intl_Warranty.pdf
Lutron and    are registered trademarks of Lutron Electronics 
Co., Inc. 
©2013 Lutron Electronics Co., Inc.
Load 
Status 
LED
Relay Toggle
Advanced 
Operations
For System Setup Guide and tools 
visit www.lutron.com
RF Relay Module
RF Relay Module Operation
Reset Factory Defaults
Note: In some instances it may be 
necessary to reset the RF Relay Module 
back to factory default settings.
A
Triple-tap the Advanced Operations 
(“ADV”) button, on the RF Relay 
Module and hold until the LED 
begins to flash slowly.
Within 3 seconds of flashing, 
release and triple-tap the button 
again and the LED will flash 
rapidly indicating that the unit has 
been reset to factory defaults.
B
Note: Any associations or programming 
previously set up with the unit will be lost 
and will need to be re-programmed.
Troubleshooting
English
When installing a RF Relay Module, 
use the supplied conduit nut and 
wire the module as shown.
If installing unit inside a junction box, 
please see Application Note #423.
For more information: www.lutron.com
Installation:  
LMJ-, LMQ-, and LMM- models
Conduit Nut
White  
(Neutral)
Black  
(Hot)
Red  
(Switched Hot)
To Load
Technical Assistance  |  1.800.523.9466  USA, Canada, and the Caribbean  |  +44.(0)20.7702.0657 Europe  |  +1.610.282.3800 Others  |  www.lutron.com   
RF Relay Module can be installed 
in a junction box or marshalling 
box (optional) using the conduit nut 
(provided) or with mounting screws 
(not provided). Please consult local 
and national electric codes for 
proper installation.
RF Relay Module Placement
RF Relay Modules must be located within 30 ft (9 m) of an RF signal repeater. RF relay modules cannot 
be controlled by the system until they are programmed using the system programming software.
Shock Hazard. May result in 
serious injury or death.  
Turn off power at circuit breaker 
before installing the unit.
WARNING
Installation:  
LMK- and LMN- models
Blue (LMK-), Black (LMN-)
(
Neutral
)
Brown (LMK-), Red (LMN-)
(
Line
)
Black (LMK-), Yellow (LMN-) 
(Switched Line)
Conduit Nut
21 mm knockout opening
To Load
For 
LMN-16R-DV-B use supplied Twist-on wire 
connectors. (3 supplied)
1
2
3
10 mm
Wiring a Lever Operated Connector (shown)
When wiring lever operated connectors (3 supplied) 
please use 14 AWG to 12 AWG (2.5 mm
2
 to 4.0 mm
2
diameter solid or stranded copper wire. 
220 - 240 V~  50/60 Hz
Load does 
not respond 
to Wireless 
Transmitter(s).
•  Ensure breaker to the 
RF Relay Module is on.
•  Ensure the load has 
been properly wired to 
the RF Relay Module.
•  Ensure that the RF 
Relay Module has been 
activated in the system.
•  Ensure that the Wireless 
Transmitter battery is 
installed correctly.
RF Relay 
Module does 
not respond 
to a keypad, 
wireless 
controller or 
sensor.
•  Improper  programming.   
Program from the 
system programming 
software.
•  Out of RF Range. 
Reposition to be within 
30 ft (9 m) of an RF 
signal repeater.
•  Already at current level. 
The RF Relay Module 
has already responded 
to a command, or is 
already at the requested 
setting.
•  Wireless controller or 
sensor batteries low 
or installed incorrectly. 
Replace or install 
batteries properly.
•  RF interference.  
Do not run RF Relay 
Module wires with 
other power wires or 
communication wires 
(e.g., networking, audio, 
or video signals).
120/277 V~  50/60 Hz (LMJ- model)
220 - 240 V
~  50/60 Hz (LMQ- and LMM- models)