FlexSmart™ 609X Series Euro Readers Installation Guide – 6090A-901, A.1 
 
 
Figure 2-5 – Fascia Label 
Wiring 
3.1  Cable Types and Maximum Lengths 
The 609x series readers require a minimum supply voltage of 9.0 VDC at the reader. Voltage drops, 
caused by the cable resistance, can be compensated by increasing the power supply voltage, provided 
the maximum supply voltage (16.0 VDC) is not exceeded at the reader.  
CAUTION: THE READER SUPPLY VOLTAGE MUST NOT EXCEED 16.0 VDC. 
 
CAUTION: DO NOT USE CABLES WITH GAUGES SMALLER THAN 24 AWG: 
The following are recommended cable types and maximum cable lengths for a cable connecting the 
power supply to the reader. 
Maximum Cable Length 
Cable Type 
200’ (61 m) 
24 AWG (0.51mm), overall foil shield, Belden 9533 series or equivalent. 
300’ (91 m) 
22 AWG (0.64mm), overall foil shield, Alpha Wire 5192C series or equivalent. 
500’ (152 m) 
18 AWG (1.02mm), overall foil shield, Alpha Wire 5382C series or equivalent.