Transmitter Setup
4.2 Analog Output
Analog Output Parameter
Specify the source parameter for the analog output.
Level is the default parameter. Ullage, Volume or
Amplitude are also available.
Minimum Output
Set the measured value that corresponds to 4 mA.
Maximum Output
Set the measured value that corresponds to 20 mA.
Alarm Selection
Set the alarm mode for the analog output current
when a measurement error occurs.
Low: the output current is set to 3.9 mA.
High: the output current is set to 22 mA.
Hold last value: the output current is set to the
measured value at the time when the error occurs.
See chapter 5 Using the Display Panel for information on how to use the Display