INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
5808W3 Photoelectronic Smoke/Heat 
Detector with Built-in Wireless Transmitter
D100-100-00 
I56-2768-000
Before  installing  detectors,  please  thoroughly  read  these 
installation  instructions  and  Manual  I56-407,  Guide  for 
Proper  Use  of  System  Smoke  Detectors,  which  provides 
detailed information on detector spacing, placement, zon-
ing, wiring, and special applications. Copies of this manual 
are available from ADEMCO.
NOTICE: This manual should be left with the owner/user 
of this equipment.
IMPORTANT: This detector must be tested and maintained 
regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.
General Description
The  5808W3  photoelectronic  smoke/heat  detector  with 
built-in  wireless  transmitter  is  intended  for  use  with 
wireless  alarm  systems  that  support  5800  series  devices. 
Refer  to  control/communicator  installation  instructions 
for  compatibility.  The  5808W3  smoke/heat  detector  can 
be used with 5881 series (L, M, H) and 5881EH receivers 
for  residential  installations.  For  commercial  installations, 
the  5881EH  receiver  should  be  used.  The  transmitter  can 
send alarm, tamper, maintenance (when control panels are 
equipped to process maintenance signals), and battery con-
dition messages to the system’s receiver. The maintenance 
signal fully complies with the sensitivity test requirement 
specified in NFPA 72, 7-2.2. Refer to the wireless system’s 
instructions for the maximum number of transmitters that 
can be supported.
The 5808W3 incorporates a state-of-the-art optical sensing 
chamber and an advanced microprocessor. The micropro-
cessor allows the detector to automatically adjust its sen-
sitivity back to the factory setting when it becomes more 
sensitive  due  to  contaminants  settling  in  its  chamber.  In 
order for this feature to work properly, the chamber must 
never  be  opened  while  power  is  applied  to  the  smoke 
detector.  This  includes  cleaning,  maintenance  or  screen 
replacement.  All  models  also  feature  a  restorable,  built-
in, fixed temperature (135°F) thermal detector and is also 
capable of sensing a freeze condition if the temperature is 
below 41°F.
The 5808W3 contains a piezoelectric horn which generates 
the ANSI S3.41 temporal pattern in an alarm condition. In 
alarm, a message is also sent to the wireless control panel 
and  the  smoke  detector’s  ID  number  is  displayed  at  the 
console. The alarm message is transmitted every 4 seconds 
until  the  smoke  or  heat  condition  has  cleared  and  the 
detector has reset. During an alarm condition, pressing the 
detectors test switch will silence the piezoelectric horn for 5 
minutes. Once the detector has reset, a RESTORE message 
is transmitted to the control panel and the ID number can 
be cleared from the panel. The built-in Drift Compensation 
algorithm  automatically  maintains  the  sensitivity  of  the 
detector. Once the detector reaches its limit of compensa-
tion,  it  transmits  a  maintenance  signal  to  the  panel.  The 
mounting base installation is simplified by the incorpora-
tion of features compatible with drywall fasteners.
Two LEDs on the detector provide a local visual indication 
of the detector’s status:
Table 1: Detector LED Modes
Green LED
Red LED
Piezoelectric Horn
Power-up
Blink 5 sec
Blink 5 sec
Off
Normal (standby)
Blink 10 sec
Off
Out of sensitivity
Blink 5 sec
Off
Freeze Trouble
Blink 10 sec
Off
Smoke Alarm
Blink 1 sec
Temporal Pattern
Thermal Alarm
---
Blink 4 sec
Temporal Pattern
Low Battery
---
Blink 45 sec
Chirp 45 sec
During an initial power-up delay, the red and green LEDs 
will  blink  synchronously  once  every  five  seconds.  It  will 
take approximately 20 seconds for the detector to finish the 
power-up cycle (see Table 2).
After power-up has completed and the detector is function-
ing  normally  within  its  listed  sensitivity  range,  the  green 
LED  blinks  once  every  ten  seconds.  If  the  detector  is  in 
need  of  maintenance  because  its  sensitivity  has  shifted 
outside the listed limits, the red LED blinks once every five 
seconds. When alarm has been activated by smoke, the red 
LED blinks every 1 second. During a thermal alarm condi-
tion  (>135°F)  the  red  LED  blinks  once  every  4  seconds. 
The  LED  indication  must  not  be  used  in  lieu  of  the  tests 
specified under Testing. In a freeze trouble condition, the 
red LED will blink once every 10 seconds (refer to Table 1). 