CAUTION
DO NOT attach the detector to removable ceiling panels. Attach the detector 
across panel support as shown in Figure 3.
TAMPER PROTECTION
This detector has a built-in tamper switch that will cause a CHECK signal to 
be displayed at the console of the detector if it is removed from its installation 
bracket. The mounting bracket can also be made tamperproof by breaking off 
the smaller tab at the scribed line (see Figure 2), thus preventing removal of 
the detector without a tool. To remove the detector, use a small screwdriver to 
depress the tamperproof tab and turn the detector counterclockwise.
TESTING
NOTE:  Before  testing,  notify  the  proper  authorities  that  the  smoke  detector 
system is undergoing maintenance and will temporarily be out of ser-
vice. Disable the zone or system undergoing maintenance to prevent 
unwanted alarms.
Detectors must be tested after installation and following periodic maintenance. 
The 5808LST may be tested as follows:
A.  TEST SWITCH
 
1.  A recessed test switch is located on the detector housing.
 
2.  Push and hold the recessed test switch for a 
minimum of 5 seconds. 
Use a small screwdriver or allen key maximum diameter of .18” (The 
alarm panel will trigger and then the smoke detector will go into alarm. If 
the tool is removed from the recessed switch the sounder will shut off.)
 
3.  The LED on the detector should blink once per second and the horn 
should sound within 3 seconds.
B.  SMOKE ENTRY TEST
 
Hold a smoldering punk stick or cotton wick at the side of the detector and 
gently blow smoke through the detector until the unit alarms.
C.  DIRECT HEAT METHOD (Hair dryer of 1000-1500 watts)
 
Direct  the  heat  toward  either  side  thermistor.  Be  sure  to  hold  the  heat 
source about 12 inches from the detector to avoid damage to the plastic. 
The detector will reset only after it has time to cool.
Smoke  detection  testing  is  recommended  for  verifying  system  protection 
capability.
A detector that fails to activate with any of these tests should first be cleaned 
as outlined in this manual’s MAINTENANCE section. If the detector still fails to 
activate, return for repair.
Notify the proper authorities that the system is back on line.
TESTING TRANSMITTER SIGNAL
NOTE: Remove battery tab before installation. 
This test should be performed before installation to determine a strong com-
munication path with the control panel and after installation is complete. Also, 
the owner/user should test the unit at least weekly.
1.  Activate the wireless system’s TEST mode from the console.
2.  Depress  and  hold  the  smoke  detector’s  TEST  switch  and  the  detector 
should immediately transmit an alarm signal to the control panel. The built-
in horn will start to sound about 2.5 seconds after depressing the button.
3.  The  wireless  system’s  console  should  emit  at  least  3  audible  sounds 
when the alarm transmission is received and will display the transmitting 
detector’s ID number.
4.  When the console has received the test signal, release the TEST switch. 
The horn will immediately stop and a few seconds later the detector’s ID 
number will clear from the console display.
5.  If the console does not respond as noted, check the polarity of the batter-
ies  and  be  sure  they  are  fresh.  If  this  is  an  initial  installation,  try  moving 
the  detector  to  another  location  that  provides  proper  reception.  Also  be 
sure  that  the  detector’s  ID  has  been  “enrolled”  by  the  control  panel  (see 
PROGRAMMING). Then, repeat the test.
6.  Turn off the system’s TEST mode from the console (security code + OFF).
CAUTION
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
WHAT TO DO IN CASE OF FIRE
1. 
DON’T PANIC — escape may depend on clear thinking.
2.  Get out of the house following the planned escape routes, if possible. Do 
not stop to dress or to collect anything.
3.  Open doors carefully only after feeling them to see if they are hot. If a door 
is hot, do not open it— follow an alternate escape route.
4.  Keep  close  to  the  floor  —  smoke  and  hot  gases  rise.  Breathe  through  a 
cloth (wet, if possible) and take short shallow breaths.
5.  Keep doors and windows closed unless it is necessary to open them for 
escape. 
6.  Meet at your meeting place after leaving your home.
7.  Call  the  local  fire  department  as  soon  as  possible  from  outside  
the home.
8.   Never re-enter a burning building.
For more information about fire safety, contact your local fire department. They 
can supply more detailed information about making your home as free from fire 
hazards as possible and about planning for escape in case of fire.
MOUNTING
First, determine the best location for the smoke detector; a location that pro-
vides strong wireless transmission paths and proper smoke detection.
 A GOOD 
TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED 
MOUNTING  LOCATION  BEFORE  PERMANENTLY  INSTALLING  THE 
DETECTOR.
  To  check,  perform  the  test  described  in  the  TESTING 
TRANSMITTER SIGNAL section of this manual. To mount the detector:
1.  Once a suitable location has been determined, install the mounting bracket 
on the ceiling or on the wall (if local ordinances permit). Use the two screws 
and anchors provided.
2.  Prior  to  mounting  the  detector  to  the  mounting  bracket,  the  system  must 
“enroll” the detector’s ID. See the PROGRAMMING section for the steps to 
follow.
3.  Turn  the  detector  in  a  clockwise  direction  in  the  mounting  bracket  until  it 
clicks into place.
4.  Test the detector immediately after completing the installation (as described 
in the TESTING section of this manual) and refer to the control system’s 
instructions for additional information concerning the use of wireless smoke 
detectors. 
 
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
TAMPER RESISTANT TAB
 (CUT OFF SMALL TAB TO
 ACTIVATE TAMPER-RESIST
 FEATURE)
ALIGNMENT
ARROWS
S0158-00
Figure 2. Detector Mounting Bracket
S0162-00
Figure 3. Mount Detector Across Ceiling Panel Support