Honeywell International Inc. 8DL5819-1 Manuale Utente

Pagina di 3
WIRING CONNECTIONS 
With the battery still not inserted, connect the shock processor 
loop (if used) to the unit's loop TB1 terminals (see Detail "B").  
The contact loops must use closed circuit devices.  TB2 can be 
used for normally closed contacts. 
Note:  If the contact loops are not used, no connection is needed 
across their terminals. 
 
"ENROLLING" THE TRANSMITTER SERIAL NUMBER 
Each 5819 Shock Processor has its own unique serial number 
permanently assigned during manufacture.  Each input of the 
transmitter also has a distinct "loop" number that must be input to 
the control panel during installation.  Assign each to an individual 
zone and designate the Input Type as "RF" (Supervised RF). 
The serial number can be input by one of the following methods: 
•  "Enrolled" by transmitting from the device during zone 
programming (pressing the tamper switch, shorting any loop, 
etc.). 
•  Entered through the keypad at the "Input S/N" or "Transmit 
Now" prompt during manual zone programming. 
•  Entered through COMPASS Downloading Software and 
downloaded to the control.   
When programming the 5819 transmitter's serial number at 
the control panel, do the following: 
1.  At the "Input Type" prompt, enter "3" for RF (Supervised RF). 
2.  When prompted for the loop number, enter the input loop you 
are using (see Diagram 2).  See the control panel's installation 
instructions for specific programming procedures. 
BATTERY INSTALLATION/REPLACEMENT 
1. 
Remove the transmitter's cover as described in Mounting, 
Step 1. 
2. 
Observe correct polarity and insert the battery provided into 
the battery holder (see Diagram 2).   
3. 
Replace the cover, engage the hooks along one edge, and 
snap shut. 
Do not bend the antenna. 
Note: 
Replace with 3V Lithium battery only:  Panasonic 
CR123A, Duracell DL123A, Sanyo CR123A, ADEMCO 
466, or Varta CR123A. 
 
BATTERY CAUTION: Risk of fire, explosion, and burns.  Do not 
recharge, disassemble, heat above 212°F (100°C), or incinerate.  
Dispose of used batteries promptly.  Keep away from children. 
 
UNIT DIMENSIONS 
4.8" H x 1.5" W x 1" D 
 
TO THE INSTALLER 
Regular maintenance and inspection (at least annually by the 
installer) and frequent testing by the user are vital to continuous 
satisfactory operation of any alarm system.  The installer should 
assume the responsibility of developing and offering a regular 
maintenance program to the user, as well as acquainting the user 
with the proper operation and limitations of the alarm system and 
its component parts.  Recommendations must be included for a 
specific program of frequent testing (at least weekly) to insure the 
system's operation at all times. 
 
 
 
 
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED FOR 
WARRANTY INFORMATION, AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM. 
 
 
FCC STATEMENT 
FCC ID: CFS8DL5819-1
 
This device complies with Part 15 of the FCC Rules. Operation is subject to the 
following two conditions: (1) This device may not cause harmful interference (2) 
This device must accept any interference received, including interference that may 
cause undesired operation. 
 
                                            CANADA: 573F-58191
 
 
 
 
 
 
 
 
 
 
 
165 Eileen Way, Syosset, New York 11791
Copyright © 2004 Honeywell International Inc.
www.honeywell.com/security