Honeywell International Inc. 8DL5853-1 Manuale Utente

Pagina di 2
 
 
 
Refer to Installation Instructions and diagrams (next page) when installing this product 
 
 
 
®
  
©2002 Pittway Corporation  All Rights Reserved 
FlexGuard is a registered trademark of Honeywell, Inc. - All other 
brands mentioned are the trademarks or registered trademarks 
of their respective owners. Specifications subject to change 
without prior notice. 
 
¬%;§l
                             5-051-735-00BX  2/02 
)OH[*XDUG
Š
 
5853 Wireless Glassbreak Detector Supplemental Information
 
1. General Information 
The 5853 Wireless Glassbreak detector with 
Transmitter senses the sound of breaking tempered, 
laminated, wired, and ordinary plate glass.  The self-
contained detector includes a transmitter that can send 
alarms, tamper signals, and low battery messages to 
the control panel.   The sensor is compatible with 5800-
series wireless hardware, and is designed for 
continuous operation using two 3V lithium batteries 
(CR-123A or equivalent; included)    
NOTE:  The 5853 is not recommended for protection of 
glass areas that are less than 10-7/8 inches by 10-7/8 
inches.  Refer to the Protected Glass Types section 
and chart for complete information. 
Prior to installation, you must: 
• 
Connect its batteries by removing the tab,  
• 
Adjust the detector’s sensitivity, and  
• 
“Enroll” the detector’s serial number.  
Refer to the following sections to install the 5853. 
 
 
2.  Connecting Batteries/Initial Power Up  
To connect the batteries, remove the tab from the end 
of the battery holder.  The detector will start its power 
up sequence, in which both the LED indicators will 
illuminate for one second.  (The LED indicators are 
described later in these instructions.) 
 
3.  Adjusting Detector Sensitivity (Range) 
The 5853 has four sensitivity settings, which are set 
using the SENS1 and SENS2 DIP switches
The settings are: 1) maximum; 2) medium; 3) 
low; and 4) lowest. By default, sensitivity is set to 
MAXIMUM.   
To change the detector’s sensitivity, use a small 
screwdriver to adjust the SENS1 and SENS2 switches, 
as shown in the table below: 
SENSITIVITY APPROX. 
RANGE * 
SENS1 SENS2 
MAX 
25 ft (7.6m) 
OFF OFF 
MEDIUM 
15 ft (4.6m) 
ON OFF 
LOW 
10 ft (3m) 
OFF ON 
LOWEST 
5 ft (1.5M) 
ON ON 
 
4.  Enrolling Detector Into 5800-Series Receiver 
Before the control panel will recognize the 5853, you 
must program the device's serial number into the 
control panel.  This process, ("enrolling") is described 
in detail in the control panel's installation instructions.   
When programming the transmitter, specify: 
• 
Input Type = 3 (Supervised RF) 
• 
Loop Number = 1 
You can transmit the device’s serial number 
automatically or enter it manually.  To transmit the 
number automatically, momentarily activate the front 
tamper switch.  To enter the serial number manually, 
refer to the control panel’s instructions to enroll the serial 
ID number which appears on the product.   
 
5.  Selecting Installation Location 
The 5853 can be mounted on the ceiling or the wall.  
Choose a mounting location that is at least 7 feet 
(2.1m) from floor and no more than 25 feet (7.6m) from 
the farthest protected glass.  Be sure the detector has 
an unobstructed line-of-sight to the protected glass!  
 
Before mounting the detector permanently, test it to 
ensure that it functions satisfactorily in the chosen 
mounting location.  Verify that the detector can detect 
glassbreak sounds, following the directions in the 
“Testing the Detector” section.  Ensure that the 5853 is 
within range of the receiver, following the instructions 
for the signal-strength test found in the control panel’s 
installation instructions.  
(To send the signal required 
by the test, activate the detector's front tamper switch.)  
If the detector fails, relocate it and repeat both tests. 
6.  Mounting the Detector 
NOTE:  If using the rear tamper and installing on dry 
wall (sheet rock),  position the detector so that the wall 
tamper is over a wall stud or ceiling joist. 
 
To mount the detector:   
1.  Using the 5853 mounting holes as a template, 
mark mounting locations on the ceiling or wall. 
2. 
If using the optional wall tamper, remove 
the batteries, then mark the wal tamper 
location through its mounting hole. 
3.  If required by the mounting location, install 
wall anchors for the mounting screws. 
4.  Secure the 5853 to the wall or ceiling, 
oriented so the microphone has the best 
line-of-sight to the protected glass. 
5.  Reinstall the batteries if previously removed. 
6.  Close and secure the detector front cover. 
 
7.  Testing the Detector 
The detector should be tested at least once each year.  
Test the detector with the GBS-7 Glassbreak Simulator.   
Other simulators will not give accurate indication of 
range.  
 
 
To enter Test Mode manually: 
1.  Open the front cover. 
2.  Use a screwdriver to short the Test Mode 
pads on the PC board (see diagram on next 
page).   
3.  Close the front cover. 
The detector’s green LED blinks approximately once per 
second to indicate that it has entered the test mode.   
 
To enter the Test Mode with the GBS-7: 
1.  Stand within 4.6 m (15 feet) of the detector. 
2.  Switch the GBS-7 to ACTIVATE and MANual 
modes. 
3.  Point the front of the glassbreak simulator 
towards the detector and press the red 
START button.   The simulator buzzes a short 
activation code. 
 
When the detector enters Test Mode, the green LED 
on the detector flashes about once per second.  If the 
green LED does not flash, move closer to the detector 
and repeat the procedure.  
 
Testing the Detector (flex and audio signals): 
To test the 5853, do the following: 
1.  Place the detector in Test Mode. 
2.  Set the GBS-7 switches to the TEST and 
FLEX positions. 
3.  Position the GBS-7 near the farthest point of 
the protected glass, and point it directly at the 
detector. If window coverings are present, 
close them fully and hold the GBS-7 between 
the coverings and the protected glass. 
4.  Press the red START button. The simulator 
clicks on and starts an eight-second armed 
period. 
5.  Generate a flex signal by carefully striking the 
glass with a cushioned tool. The GBS-7 
responds with a burst of glassbreak audio.   
If the detector receives both the flex and audio signals 
properly, its red Alarm LED lights for 5 seconds. (Red 
Alarm LED does not latch.) 
   
Testing the Detector (audio signals only): 
The GBS-7 can also be used to test the detector’s 
ability to receive audio signals only.  See the GBS-7 
Operating Instructions for additional information.  When 
it receives the audio signal, the detector flickers its 
green Event LED.  
 
Exiting Test Mode: 
When you have finished testing, exit Test Mode by 
following the same procedure used to enter Test Mode.  
The detector automatically exits Test Mode after five 
minutes if no events are detected. 
 
8.  LED Indicators 
The detector is equipped with two LEDs: a green Event 
LED and a red Alarm LED.  When the LEDs are 
enabled during testing, they light in a variety of patterns 
to convey the detector’s operational status.  The 
following table summarizes the LED messages.  
(Please note that the LEDs are only enabled during 
Test Mode, and are inactive during normal operation.) 
 
CONDITION GREEN 
LED 
RED 
LED 
Power up 
ON 1 second 
ON 1 second 
Test Mode 
Flash once per sec 
OFF 
Test Mode, event detected 
Flicker 
OFF 
Test Mode, alarm 
Flash once per sec 
ON 5 seconds 
Low Battery * 
Flash once per sec 
Flash once per sec 
* If battery voltage drops too low, LEDs are no longer visible. 
9.  Cover Screw 
The front cover can be secured after installation.  To do 
so, remove the cover breakout flash (illustration on next 
page) and secure the front cover with a ¼-in., #4 
(2.2mm) screw (supplied). 
 
10.  Maintaining Proper Operation 
To maintain the 5853 Glassbreak Detector in proper 
working order, please observe the following: 
Replace the batteries when the system indicates a low 
battery condition (refer to the control panel’s operating 
instructions.)  Be sure to replace the batteries with the 
proper type and voltage, and ALWAYS replace both 
batteries at the same time. 
This device should not be relocated without the advice 
or assistance of the alarm service company. 
Fans, air conditioners, blowers, loudspeakers, or other 
sources of vibration and sound should not be 
introduced into the protected area after installation of 
glassbreak detectors.  If unavoidable, contact the alarm 
service company; re-adjust/re-test the equipment as 
needed. 
 
11.  Protected Glass Types Chart 
 
NOTE:  The 5853 is NOT recommended for protection of glass 
areas smaller than 10-7/8 inches x 10-7/8 inches. 
 
Nominal Thickness 
 
Glass Type* 
Minimum Maximum 
 
Plate 
2.4mm (3/32 in.) 
10mm (3/8 in.) 
Tempered 
3mm (1/8 in.) 
10mm (3/8 in.) 
Laminated
1
 
3mm (1/8 in.) 
14mm (3/8 in.) 
Wired 
6mm (1/4 in.) 
6mm (1/4 in.) 
Coated
2
 
3mm (1/8 in.) 
6.4mm (1/4 in.) 
Sealed Insulating
1
 
3mm (1/8 in.) 
6mm (1/4 in.) 
 
Minimum size for all types is 28cm (11 in.) square; glass must be 
framed in the wall or mounted in a barrier at least 0.9m (36 in.) wide.  
1  
Protected only if both plates in the unit are broken 
2  
Coated glass with security films, including films for solar protection, up 
to 12 mi., thick may be used.   Film Technologies, Inc.'s GLASS 
GARD
®
 GLL 1200 has been evaluated with this product by 
Underwriters Laboratories Inc. at ADEMCO's request. 
 
12. Specifications
 
Power: 
Two 3 V Batteries (included). Replace only with ADEMCO # 
466, Panasonic CR123A, Sanyo CR123A, Duracell DL123A, or 
Varta CR123A (Lithium Manganese Dioxide) 
 
Maximum/Minimum Ranges:   
Maximum range is 25 ft (7.6m) from farthest protected glass. 
No minimum range. 
 
Operating Temperature: 
14° to 122° F (-10° to 50° C) 
 
Accessories: 
ADEMCO GBS7 Glassbreak Simulator 
 
13.  NOTICES 
FCC NOTICE     FCC ID:  CFS8DL5853-1 
This device complies with Part 15 of FCC rules.  Operation is subject to the 
following two conditions:  (1) This device may not cause harmful interference, 
and (2) this device must accept any interference received, including 
interference that may cause undesired operation.   
 
CANADA: 1748A-58531
TO THE INSTALLER Regular maintenance and inspection (at least annually) by the  
installer and frequent testing by the user are vital to continuous satisfactory 
operation of any alarm system.  The installer should assume the responsibility of 
developing and offering a regular maintenance program to the user as well as 
acquainting the user with the proper operation and limitations of the alarm 
system and its component parts.  Recommendations must be included for a 
specific program of testing (at least weekly) to ensure the system’s proper 
operation at all times. 
 
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE 
RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED FOR 
DETAILS REGARDING WARRANTY INFORMATION AND 
LIMITATIONS OF THE ENTIRE ALARM SYSTEM. 
 
 
 
To test, you must first place the detector in test mode.
Add:  When ceiling mounted, the microphone
should be pointed toward the glass being 
protected.
3 In compliance with Underwriters Laboratories of
Canada's Standard for Intrusion Detection Units
(CAN/ULC-S306-M89): 
a. Plate glass 3 mm (1/8 in.) to 10 mm (3/8 in.)
can be used.
b. ULC recognizes a maximum range for
protecting sealed insulated glass and coated glass
of 2.3 m (7.5 ft.).  Sensitivity should be set at Max.