ADEMCO 5881EN Series RF Receiver – Installation Instructions
 
 
 
INTRODUCTION
 
The 5881EN RF Receiver is designed for use with control panels that support an RF receiver connection via the keypad terminals. 
• 
The 5881EN Series Receivers recognize alarm, status, and keypad control messages from 
wireless transmitters operating at 345MHz.  
• 
One  or  two  individually  identified  receivers  can  be  employed,  depending  on  the  control 
used.  Connection  of  multiple  receivers  to  a  control  can  provide  redundant  coverage  or 
extend coverage in large area. 
• 
The  5881EN  features  a  Spatial  Diversity  system that  virtually  eliminates  the  possibility  of 
"Nulls" and "Dead Spots" within the coverage area. 
• 
The  5881EN  uses  ADEMCO’s  High  Security  technology,  and  can be  used  in commercial 
fire installations.  
 
The 5881ENHC receiver contains front and back tamper that permits its use in commercial 
burglary and fire installations.
 
UL 
For 5881ENHC Receivers: 
• 
In  commercial  fire  applications,  the  receiver  can  only  be  used  with  control  panels  that  are 
approved  for  use  in  Commercial  Fire  Installations.  When  the  5881ENHC  is  used  in 
commercial fire applications, DIP switch 5 must be in the ON position. 
•  In commercial burglary applications, the 5881ENHC can only be used with control panels that 
are approved for use in Commercial Burglary Installations. 
•  In commercial fire applications, a keypad must be connected to Keypad Port 2 in the control. 
The  keypad  must  be  mounted  on  the  control  or  within  3  feet  of  the  control  with  the  wiring 
encased in conduit. 
•  All power-limited wiring must be separated from non-power limited and high-voltage wiring by 
¼" (6.4mm). 
KEYPAD
TERMINALS
ON
CONTROL
BOARD
*CONTROL MUST BE CAPABLE OF
SUPPORTING A 5800 RF SYSTEM
5881ENHC
RECEIVER
TO
BURGLARY
DEVICES
5800 SERIES
WIRELESS
TRANSMITTERS
5881EN-005-V0
CONTROL
PANEL*
ECP
ISOLATOR
TO FIRE DEVICES
 
Figure 1. 5881EN Receiver System Overview 
Mounting UL Commercial Fire Applications 
NOTE: For UL-864 Fire installations, ECP Isolator (PN ECP-ISO) is required. 
• 
Each receiver supports the number of zones shown below. 
5881ENL up to 8 zones 
5881ENM  up to 16 zones 
5881ENH  *see below 
5881ENHC  *see below 
*  The number of zones that the 5881ENH receiver can support depends on the 
control with which it is used. See the control panel’s instructions for specific details.
 
If a receiver is connected to a system in which more than the permitted number of wireless zones have been programmed, a "SET UP ERROR" message (on alpha keypads) or an "E4” or 
“E8" message (on fixed-word keypads) will be displayed on the system's keypad, and none of the zones will be protected. 
The instruction manual that accompanies the control includes recommendations regarding receiver and transmitter locations, the types of wireless zones that can be programmed (e.g., 
ENTRY/EXIT, PERIMETER, INTERIOR, etc.) and the procedure for programming the receivers. 
These receivers should not be installed in an area subject to environmental extremes of below freezing  (such as an unheated warehouse) or extremely high temperatures (such as an 
attic). 
INSTALLATION 
With some controls, a receiver may be mounted directly inside the control's cabinet (receiver circuit board only, without its plastic housing) instead of remotely (in its own housing). In both 
cases, avoid mounting the receiver antennas against a metal surface. 
NOTE: You may only mount the 5881ENHC its own plastic housing. If you attempt to mount the 5881ENHC in the control’s cabinet, the receiver constantly reports a tamper condition. 
 
Mounting 
1. Remove the receiver's cover by inserting a screwdriver blade in the slot at the center of the cover's lower edge. 
2.  If the receiver is to be mounted within the control's cabinet (refer to Figure 2): 
a.  Remove the receiver's circuit board from its base by bending back the two flexible plastic tabs that hold the 
board's lower edge. 
b.  In the control's cabinet, unfasten and move the control circuit board downward (if already installed). 
c.  Hang  two  mounting  clips  (provided  with  the  receiver)  on  the  raised  cabinet  tabs,  as  shown  in  Detail  B  of 
Figure 2. 
d.  Insert the top of the receiver board between the rows of slots at the top of the cabinet, as shown in Detail A. 
e.  Position the base of the receiver board onto the mounting clips and secure to the cabinet using the screws 
supplied. See Detail B. 
f.  Hang two mounting clips (supplied with control board), on the raised cabinet tabs see Detail C in Figure 2. 
g.  Insert the top of the control board into the slots of the mounting clips secured in step e above. 
h.  Position the lower end of the control board into place on the mounting clips and secure both to the cabinet 
with the two supplied screws.  
i.  Insert  both  grounding  lugs  (supplied  with  the  receiver)  through  the  top  of  the  cabinet  into  the  left-hand 
terminals of the antenna blocks (located on the upper edge of the receiver board), and secure them to the 
cabinet with the screws provided, as shown in Detail D. 
j.  Insert  the  receiver’s  antennas  through  the  top  of  the  cabinet,  into  the  blocks’  right-hand  terminals,  and 
tighten the screws. 
k.  Affix the receiver's Summary of Connections label to the inside of the control's cabinet door. 
l.  Discard the receiver's unused plastic cover and base. 
3.  If the receiver is to be located remotely from the control in its own plastic enclosure (not in a cabinet) you will 
not need the circuit board mounting clips, grounding lugs and screws included with the receiver. 
a.  If  concealed  wiring  is  to  be  used,  route  it  through  the  rectangular  opening  at  the  rear  of  the  base  before 
mounting. For surface wiring entry, a thin breakaway area is provided along the base's right edge. 
b.  Mount the receiver in the selected location. For greatest security, use all four mounting holes (two key slot 
holes and two round holes) provided in the plastic base.  
c.  If installing a 5881ENHC, install a flat-head screw (supplied) in the case tamper tab as shown in Figure 3. 
When  the  receiver  is  pried  from  the  wall,  the  tamper  tab  will  break  off  and  remain  on  the  wall.  This  will 
activate a tamper switch in the receiver and cause generation of a tamper signal. Note that this signal will 
also be generated when the receiver’s front cover is removed. 
d.   Affix the receiver's Summary of Connections label to the inside of the housing cover. 
4.  Setting the DIP switches (All Receivers):  
a.  Set the receiver's DIP switch (#2 through #4) to identify the receiver's address (refer to the DIP switch chart 
in the Summary of Connections Diagram below). 
b.  Verify that DIP switch #1 is in the OFF position. 
c.  Set DIP switch #5 according to the following chart. 
DIP SWITCH #5 
 
For . . . 
Set to . . . 
Commercial Fire Applications 
ON 
Non-commercial Fire Applications 
OFF 
NOTES: 
• 
If  multiple  receivers  are  used  on  one  control,  DIP  switch  #5  must  be  set  to  the  same  position  on  all 
receivers. 
• 
DIP switch #5 reduces sensitivity during supervision message reception. For commercial fire applications, 
DIP switch #5 must be in the ON position. 
5.  Insert the wiring plug (with 4 flying leads) into the mating socket on the receiver (see Summary of Connections 
Diagram  below  for socket  location).  Connect  the  4  wires to  the  control's  corresponding keypad  terminals  (see 
“Interface Wiring” in the SPECIFICATIONS section below). 
6.  Install the antennas in the right-hand terminals of the two terminal blocks at the upper edge of the circuit board, 
one into each block’s right-hand terminal, and tighten the screws to secure them.  
 
Caution: Avoid mounting the receiver antennas against a metal surface. 
7.  Replace the unit's front cover using the supplied screw to secure it. 
8.  Proceed with any programming of the control that may be necessary for RF operation, and the installation of the 
system's  wireless  transmitters,  as  described  in  the  control's  installation  and  setup  guide  and  the  transmitter's 
installation instructions. 
 
NOTES: 
•  The receiver can support up to 16 high security (encrypted) wireless transmitters (keys). The total quantity of 
wireless keys (encrypted and unencrypted) that can be used is determined by the control panel. 
•  Wireless key buttons must be enrolled to zones in the control panel via zone programming first. If the wireless 
key is to be used for arming and disarming the VISTA-40 and up, a user number must then be assigned to 
the  wireless  key  via  user  programming.  If  it  is  not  done  in  this  order,  you  will  be  unable  to  respond 
successfully to the RF button zone number prompt in user programming. 
•  If more than one receiver is being used and you are using encrypted wireless keys, we recommend that you 
(a) enter the GO/NO GO mode, (b) disconnect one receiver, (c) enroll all encrypted keys into the connected 
receiver,  (d)  reconnect  the  disconnected  receiver,  (e)  exit  the  GO/NO  GO  mode,  and  then  (f)  repeat  (a) 
through (e) for the receiver that was disconnected.  
•  The  RED  LED  located  on  the  receiver's  circuit  board  should  be  used  as  an  indicator  of  strong  local  radio 
frequency interference. If this LED is continuously illuminated, the receiver should be relocated. 
• 
After  a successful  enrollment  of  an  encrypted  key,  the  GREEN  LED  blinks the  number  of spaces  that  are 
free for additional encrypted key enrollment. 
9.  Replace the receiver's cover. 
Remove Screw
And Pry Open
RECEI
VER
CIRC
UIT
BOAR
D
Board
Supporting
Slots
Holes For Antennas
And Grounding Lugs
DETAIL B
Side View
Of Mounting
Clip
DETAIL C
Side View
Of Mounting
Clip
DETAIL A
Side View
Of Board 
Supporting
Slots
Circuit
Board
Cabinet
CON
TRO
L CI
RCU
IT
BO
ARD
58
81
EN
Locking Tab
58
81E
N
-0
04-V0
 
Figure 2. 
Installing the Receiver Board in Control’s Cabinet 
 
 
5881ENHC-001-V0
SCREW
 
Figure 3: Tamper Protection 
 
Screw
58
81
EN
Locking
Tab
58
8
1
EN-00
3
-V0
Mounting
Screws
4 (Typ)
ECP
Connection
Front Tamper
(Rear Tamper)
 
Figure 4: 5881EN Remote Mounting