Honeywell International Inc. 8DLLYNXREN-5 Manuale Utente
–17–
Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form
to record the data for this installation. Note that both keypad LEDs flash while in Programming mode.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form
to record the data for this installation. Note that both keypad LEDs flash while in Programming mode.
Note: Entering a number other than the one specified will give unpredictable results.
✻
20
Installer Code
Enter 4 digits, 0-9
The Installer Code is used to enter the 4-digit Master Security Code. See
"Master Code" in the System Operation section for procedure.
Note: LYNX does not allow duplication of Installer code. If a duplicate
"Master Code" in the System Operation section for procedure.
Note: LYNX does not allow duplication of Installer code. If a duplicate
code is entered the entry is rejected and LYNX issues single long
beep indicating rejection. The old installer code remains
unchanged.
beep indicating rejection. The old installer code remains
unchanged.
✻
21
Quick Arm Enable
0 = do not allow quick arm
1 = allow quick arm
If enabled, security code is not required to arm the system. The user
simply presses and holds down the AWAY or STAY key to arm.
simply presses and holds down the AWAY or STAY key to arm.
✻
22
Keypad Backlight Timeout
0 = no timeout; always backlight keys
1 = turn backlighting off after inactivity
This option allows the choice of either always backlighting the keypad or
turning the backlighting off after 10 seconds of keypad inactivity.
turning the backlighting off after 10 seconds of keypad inactivity.
✻
23
Forced Bypass
0 = no forced bypass
1 = provide automatic bypass of all open (faulted)
zones
All zones bypassed by this function will be displayed after the bypass is
initiated.
initiated.
Note: UL installations: must be 0 (no forced bypass)
✻
24
RF House ID Code
00 = disable all wireless keypad usage
01-31 = House ID
The House ID identifies receivers and wireless keypads.
If a 5804BD/5804BDV Transmitter is to be used, a House ID Code MUST
If a 5804BD/5804BDV Transmitter is to be used, a House ID Code MUST
be entered, and the keypad should be set to the same ID.
✻
25
Powerline Carrier Device (X-10) House ID
0 = A
4 = E
8 = I
# + 12 = M
1 = B
5 = F
9 = J
# + 13 = N
2 = C
6 = G
# + 10 = K
# + 14 = O
3 = D
7 = H
# + 11 = L
# + 15 = P
Powerline Carrier Devices require a House ID. This field identifies this
House ID to the Control. The Powerline Carrier Devices are
programmed in field
House ID to the Control. The Powerline Carrier Devices are
programmed in field
✻80.
✻
26
Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter
zone when Chime mode is activated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime mode on)
This option allows the installer to define the specific zones intended to
chime when faulted while the system is in Chime mode. If enabled, these
zones are defined in zone list 3 (see
chime when faulted while the system is in Chime mode. If enabled, these
zones are defined in zone list 3 (see
✻81 Zone List Menu Mode).
✻
27
Real Time Clock Display
0 = do not display the time
1 = display the time
Refer to the User’s Manual for setting the clock time and date.
✻
29
Daylight Savings Time Start/End Month
0, 0 = no daylight saving time used
1-12 = start month and end month
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
✻
30
Daylight Savings Time Start/End Week
0 = disable
4 = fourth weekend
1 = first weekend of month 5 = last weekend
2 = second weekend
6 = next to last
3 = third weekend
7 = 3
rd
from last
Enter the appropriate start and end weekend of the month.
✻
31
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming period for
a given zone
UL installations: must be 0 (no limit)
This field applies only to burglary zones (zone response types 1-5, 10).
This field applies only to burglary zones (zone response types 1-5, 10).
Notes: 1. This field applies only to the bell and does not affect keypad
sounds.
2. If swinger shutdown occurs (see Swinger Shutdown in Field
✻92), the number of alarm soundings on a given zone will be
limited by the setting selected in Field
limited by the setting selected in Field
✻92.
✻
32
Fire Sounder Timeout
0 = yes, fire sounder timeout after time programmed in
field
✻
33
1 = no fire sounder timeout; continue sounding until
manually turned off
This Control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses. . .
✻
33
Alarm Bell Timeout
0 = No timeout
2 = 8 min
4 = 16 min
1 = 4 min
3 = 12 min
This field determines whether the external sounder will shut off after
time allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
time allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)