Honeywell International Inc. 8DLLYNXREN-5 Manuale Utente

Pagina di 72
  
 
–53– 
Testing the System 
 
Test Mode
After installation is completed, the security system should be carefully tested, as follows. 
1.  With the system in the disarmed state, check that all zones are intact. If the READY LED is not lit, 
press the [
 ✻
] key to display the faulted zone(s). Restore faulted zone(s) if necessary, so that READY 
LED lights. Fault and restore every sensor individually to assure that it is being monitored by the 
system. 
2. Enter 
the 
security code and press the TEST key.  The outside sounder will sound for 1 second and all 
the LED segments on the keypad display light for 3 seconds. LYNX announces the zone’s voice 
descriptor (if programmed) followed by 3 beeps, each time a contact is faulted.  A test report will be 
transmitted to the central station immediately. If the backup battery is discharged or missing, the 
sounder may not turn on and a LOW BATTERY report will be transmitted with a TEST report. The 
keypad will beep once every 45 seconds as a reminder that the system is in the Test mode.  
3.  To turn off the Test mode enter security code and press the OFF key. 
Notes:  (1)  Triggering a zone set to Arm AWAY, Arm STAY, or Disarm will take the system out of Test and cause that action. 
 
(2)  BR type transmitters do not display during Test mode (keypad beeps only) 
 
(3)  Macros cannot be run from the Test mode. 
 
(4)  Test mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55 minutes of Test mode), “TEST” 
flashes on the keypad indicating that the end of Test mode is nearing. 
 
(5)  Upon termination of a test mode all faulted 24-hour zones are treated as a trouble zones.
 
 
Armed System Test
Alarm messages will be sent to the central station during the following tests 1 and 2. Notify 
them in advance that tests will be in progress. 
1.  Arm the system and fault one or more zones. After 15-45 seconds (if optional burglary abort window is 
selected), silence alarm sounder(s) by entering the code and pressing OFF.  Check entry/exit delay 
zones. 
2.  Check the keypad-initiated alarms that are in the system by pressing the Panic key pairs. If the system 
has been programmed for audible emergency, the keypad will emit a steady alarm sound, and 
ALARM” and zone number will be displayed. Silence the alarm by entering the security code and 
pressing OFF. 
If the system has been programmed for silent emergency, there will be no audible alarms or displays, 
but a report will be sent to the central station. 
3.  If Powerline Carrier Devices have been installed, test their programmed action. 
4.  Notify the central station when all tests are finished, and verify results with them. 
5.  To test the wireless part of the system and the RF receiver, perform the two additional tests described 
in the Installing Wireless Zones section: Sniffer mode and Go/No Go Test. 
 
Note:  System Test mode (installer/master code + test) and Go/No Go Test (installer code + # + 8) will be 
automatically terminated after 3-1/2 to 4 hours if the installer or user does not manually terminate it. 
This ensures that fire and panic zones will not remain disabled. However, Sniffer mode (installer code + # 
+ 3) does not automatically expire.  You must manually exit (Installer/User Code + OFF) Sniffer 
mode to return to normal operation. 
 
 
TO THE INSTALLER 
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are 
vital to continuous satisfactory operation of any alarm system. 
The installer should assume the responsibility of developing and offering a regular maintenance program to 
the user as well as acquainting the user with the proper operation and limitations of the alarm system and its 
component parts. Recommendations must be included for a specific program of frequent testing (at least 
weekly) to ensure the system’s proper operation at all times.