142134 
6.7.2  22R08A Output Relay Connections 
!
 
WARNING
 
Verify that the main input power is OFF before attempting to make connections. 
 
All relay outputs are capable of operating up to 8 Amp, 240 VAC, or 12 VDC circuits. Connecting to 
equipment or contactors with higher voltage or current ratings requires an intermediate relay.  
Total sustained current must not exceed 10 Amps for relays K5 through K8. 
Note:   When connecting to inductive loads such as relay coils and motors, Laird recommends that 
snubbers be placed across the load in order to ensure reliability and long life of the output relay 
contacts.