MAINTENANCE
The W4 detector reports maintenance issues to the control panel and com-
municates them visually and audibly per Table 2.
Trouble feature: When the sensor (supervision) is in a trouble condition (such 
as a detector that is dirty or CO sensor non-functioning), the detector will 
send a trouble signal to the panel. Depending on the issue, the detector must 
then be serviced or replaced.
CO sensor end-of-life timer feature: When the CO sensor has passed end-of-
life, a trouble signal will be sent to the panel. This indicates that the CO sensor 
inside the detector must be replaced. If unresolved for 30 days, the detector 
will chirp intermittently. The typical life of the CO sensor is ten years from the 
date of manufacture; it is recommended to periodically check the “Replace 
by” sticker located on the back of the detector head.
Batteries: WARNING: Use only Duracell DL123A or Panasonic CR123A lithium 
Batteries may present risk of fire or explosion. Remove all old batteries, wait 
10 seconds then insert four new batteries.
NOTE: Before performing any maintenance on the detector, notify the proper 
authorities that maintenance is being performed and the system will be tem-
porarily out of service. Disable the zone or system undergoing maintenance 
to prevent any unwanted alarms. Power must be removed from the detector 
before performing maintenance of any kind.
CLEANING
1.   Remove the detector head by turning counterclockwise.
2.   Clean the outside casing with a cloth. Ensure that the holes on the front 
of the alarm are not blocked with dirt and dust. Canned air can be used 
to remove any dust or debris.
3.   Reattach the detector head to the mounting base by rotating clockwise. 
FIGURE 2: TEST BUTTON LOCATION AND OPERATION
 
 
S0338-00
SMOKE ENTRY TEST / SMOKE SENSITIVITY READOUT
To smoke test W4, because it is a multi-criteria detector), it must be put into 
the smoke test mode as follows: 
1.   With the detector in standby mode, press and hold the smoke test button 
for 3 to 5 seconds. The W4 will provide diagnostic information including 
sensor status and smoke sensitivity reading and will prompt for smoke 
entry and annunciate per Table 2. 
2.   While W4 is in smoke entry mode with its green LED flashing, spray 
canned smoke into the detector. The canned smoke that can be used is 
approved for test include: Home Safeguard Industries 25S, SDi CHEK02 
and CHEK06, SDi SOLOA4, and SDi SMOKESABRE". 
3.   When the detector senses the presence of the smoke, the detector will 
sound and illuminate per Table 2 and a smoke alarm signal will be sent 
to the control panel with a test indication. 
4.   Verify the smoke alarm signal was received by the control panel.
FUNCTIONAL GAS TEST
Solo C6 brand canned CO may be used to verify the detector’s ability to sense 
CO by utilizing the RealTest® feature as follows:
1.   Press and hold the CO test button for 3 to 5 seconds. The green LED will 
start blinking rapidly indicating tshe detector is in RealTest® mode. (If the 
detector will not go into RealTest® mode, the CO sensor may be in fault 
or at end-of-life.)
2.   While the green LED is blinking rapidly, spray a small amount of canned 
CO directly into the CO gas entry port. (See Figure 3.)
3.   The detector will go into CO alarm and send an alarm to the channel 
panel if the gas entry was successful and the CO sensor is detected it-
functioning properly.
4.   Verify the smoke CO alarm signal was received by the control panel.
5.   The CO test will automatically clear when the CO clears from the sensor 
or in 30 seconds if no CO was introduced.
TABLE 2: LED INDICATION & SOUNDER DURING TEST AND MAINTENANCE
MODE
STATUS LED (TOP)
LED 
WINDOWS 
(SIDE)
SOUNDER
SPEAKER
Smoke Alarm System Test – Waiting for smoke entry 
(Press and hold Smoke test button 3-5 seconds)
Blink green  
once a second
Dark
Silent
Voice instructions for testing including warning of alarm 
signal
Smoke Alarm System Test (Upon successful smoke 
entry)
Blink red  
every 10 seconds
Blink red
Temp-3
Voice smoke warning
RealTest® Functional CO gas entry test - Waiting 
for gas entry (Press and hold CO test button 3-5 
seconds)
Blink green  
once a second
Dark
Silent
Voice instructions for testing including warning of alarm 
signal
RealTest
®
 Functional CO gas entry test -Upon 
successful gas entry
Blink red  
every 10 seconds Blink blue
Modified 
Temp-4
Voice carbon monoxide warning
Low Battery
Blink Amber  
every 45 sec
Dark
Chirp Every 
45 seconds 
after 7 days
Voice instructions by pressing either test button
Smoke Maintenance
Blink Amber  
every 5 seconds
Dark
Silent
Voice smoke maintenance instructions if Smoke test button 
is pressed
CO Trouble
Blink Amber  
every 5 seconds
Dark
Silent
Voice CO maintenance instructions if CO test button is 
pressed
CO End of Life - First 29 days
Blink Amber  
every 3 seconds
Dark
Silent
Voice end of life instructions if CO test button is pressed
CO End of Life - 30 days after panel notification
Blink Amber  
every 3 seconds
Dark
Chirp Every 
45 Seconds Voice end of life instructions if CO test button is pressed
  