SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:E 11/9/2017
31
Agency Approvals
Wireless Devices
Base+1 address will use:
Type Code Label: Control
FlashScan Type: Control
Wireless related trouble events described in Section 3.6.3 will be indicated at the base address.
The end of line supervision of the monitor input and the power monitoring of the external 24VDC supply will be indicated at the base+1 
address. 
The following table indicates the output state. 
    
For more information on the LED indicators, refer to Section 3.6.2.
3.2  Agency Approvals
3.2.1  FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 
1.
This device may not cause harmful interference. 
2.
This device must accept any interference received, including interference that may cause undesired operation.
3.2.2  Industry Canada
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: 
1.
This device may not cause interference, and 
2.
This device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est 
autorisée aux deux conditions suivantes : 
1.
L'appareil ne doit pas produire de brouillage, et 
2.
L'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre 
le fonctionnement.
IC: 573X-WFSSD for detectors, IC: 573X-WFSMM for the monitor module, and IC: 573X-WFSRM for the relay module
3.2.3  Federal Institute of Telecommunications
This device utilizes the Honeywell915 rev A radio module and complies with IFETEL standard(s).
IFT: RCPHOSW14-1983
3.3  Specifications
The following are the specifications for the wireless devices.
Base Address
Base+1 Address
Control Output Signal
Synchronization Output Signal
OFF
OFF
Low (inactive)
Low (inactive)
ON
OFF
High (active)
Strobe Only (Audible Silenced)
ON
ON
High (active)
Strobe & Audible active
OFF
ON
High (active)
Magnet Test mode
NOTE:
1. To configure a NAC circuit, with audible and visual units, to silence only the audible component with a signal silence command, configure 
both addresses to activate for the alarm condition. The base address shall be non-silenceable and the base+1 shall be silenceable with the 
appropriate resound settings.
2. When the sync module is being used for delivering only the synchronization signal (i.e. applications with the MDL3 or the ACPS-610), it is 
recommended to leave the base address point constantly active to eliminate any delay in initial synchronization.
NOTE: When a wireless relay, wireless AV base, or wireless sync module is in use, module device count must be limited to 109 modules 
per loop. This includes wired and wireless modules that are on the same loop. The module address range must be within 1-109.
!
WARNING: DO NOT MAKE CHANGES TO THE EQUIPMENT.
CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE MANUFACTURER COULD VOID THE USER’S 
AUTHORITY TO OPERATE THE EQUIPMENT.
Specification
Data
Radio Frequency
Lower ISM Band (902-928 MHz)
Maximum power output
+17dBm
Minimum signal strength level needed at the receiver for a primary path 
with weak link trouble reporting enabled.
-55dBm
Table 3.1  Wireless Device Specifications