SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C 5/8/2015
3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be 
connected to the fire alarm control panel.
  Disconnect all 
sources of power before servicing.  Control unit and associ-
ated equipment may be damaged by removing and/or insert-
ing cards, modules, or interconnecting cables while the unit is 
energized.  Do not attempt to install, service, or operate this 
unit until manuals are read and understood. 
CAUTION - System Re-acceptance Test after Software 
Changes:
 To ensure proper system operation, this product 
must be tested in accordance with NFPA 72 after any pro-
gramming operation or change in site-specific software.  Re-
acceptance testing is required after any change, addition or 
deletion of system components, or after any modification, 
repair or adjustment to system hardware or wiring. All compo-
nents, circuits, system operations, or software functions known 
to be affected by a change must be 100% tested.  In addition, 
to ensure that other operations are not inadvertently affected, 
at least 10% of initiating devices that are not directly affected 
by the change, up to a maximum of 50 devices, must also be 
tested and proper system operation verified.  
This system meets NFPA requirements for operation at 0-49º 
C/32-120º F  and at a relative humidity  93% ± 2% RH (non-
condensing) at 32°C ± 2°C (90°F ± 3°F).   However, the useful 
life of the system's standby batteries and the electronic com-
ponents may be adversely affected by extreme temperature 
ranges and humidity.  Therefore, it is recommended that this 
system and its peripherals be installed in an environment with 
a normal room temperature of 15-27º C/60-80º F. 
Verify that wire sizes are adequate for all initiating and indi-
cating device loops.  Most devices cannot tolerate more than a 
10% I.R. drop from the specified device voltage. 
Like all solid state electronic devices, this system may 
operate erratically or can be damaged when subjected to light-
ning induced transients.  Although no system is completely 
immune from lightning transients and interference, proper 
grounding will reduce susceptibility. Overhead or outside aerial 
wiring is not recommended, due to an increased susceptibility 
to nearby lightning strikes.  Consult with the Technical Ser-
vices Department if any problems are anticipated or encoun-
tered. 
Disconnect AC power and batteries prior to removing or 
inserting circuit boards.  Failure to do so can damage circuits. 
Remove all electronic assemblies prior to any drilling, filing, 
reaming, or punching of the enclosure. When possible, make 
all cable entries from the sides or rear.  Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, or printed circuit board location. 
Do not tighten screw terminals more than 9 in-lbs.  Over-
tightening may damage threads, resulting in reduced terminal 
contact pressure and difficulty with screw terminal removal. 
This system contains static-sensitive components.  
Always ground yourself with a proper wrist strap before han-
dling any circuits so that static charges are removed from the 
body.  Use static suppressive packaging to protect electronic 
assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to 
avoid damage to the control panel and associated equipment. 
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can 
radiate radio frequency energy and if not installed and 
used in accordance with the instruction manual may 
cause interference to radio communications. It has been 
tested and found to comply with the limits for class A 
computing devices pursuant to Subpart B of Part 15 of 
FCC Rules, which is designed to provide reasonable 
protection against such interference when devices are 
operated in a commercial environment. Operation of this 
equipment in a residential area is likely to cause interfer-
ence, in which case the user will be required to correct 
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits 
for radiation noise emissions from digital apparatus set 
out in the Radio Interference Regulations of the Cana-
dian Department of Communications.  
Le present appareil numerique n'emet pas de bruits radi-
oelectriques depassant les limites applicables aux appa-
reils numeriques de la classe A prescrites dans le 
Reglement sur le brouillage radioelectrique edicte par le 
ministere des Communications du Canada.  
HARSH™NIS™NOTI•FIRE•NET™, eVance™, and SWIFT™ are all trademarks; and Acclimate® Plus™FlashScan®FAAST Fire Alarm Aspiration
Sensing Technology®,
  Intelligent  FAAST®, NOTIFIER®,  ONYX®,  ONYXWorks®,  VeriFire®, and VIEW® are all registered trademarks of Honeywell
International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. The Chrome™ browser is a trademark of Google Inc.   
©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.