Honeywell International Inc. WFSSM Manuale Utente

Pagina di 64
58
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
LED Indicators
LED Pattern
Condition
Action Required
Legend
Number of blinks
LED color
Interval between blink patterns
Duration of LED state
Indicates value is approximate
Two blinks in this pattern
First blink is green. Second is yellow
7 seconds between blink patterns
Will transition to next state after 
approximately 20 minutes
Example:
All units are in seconds. Minute is indicated by “M”.
le
ddev2
_
3.
0.
wm
f
7
20
M
Figure D.4  Device LED Patterns (Continued)
Battery Check: all 
batteries present
Searching for mesh 
(in rescue mode)
Profile 
modification
1st mesh 
restructuring
Normal mode
Searching for mesh 
(in formation mode)
Minimum of 6 months battery life 
remaining
Device has a profile and can be set as a 
distributor or have profile removed
Mesh is formed and initializing
Device is in the mesh and may be in 
trouble
Profile is assigned and device is 
searching for the mesh
Profile is assigned and device is 
searching for the mesh.
Tamper entry
Device has just been tampered
Ensure the mesh is in rescue mode or wait for 
timeout to search mesh in formation mode.
Discovered mesh
Device discovered the mesh
60
Solid
2.5
Use SLC address dials to enter desired mode.
90
3
Ensure the mesh is in formation mode
25
6
5
M
Refer to the FACP to identify the trouble and 
possible resolution. 
18
4
Ensure detector is seated in the base and the 
module has a faceplate
Solid
6
5
Solid
Waiting for a profile
Searching for a profile
Pending site survey
Active/Alarm state
Battery Check: 
weak
Device is in factory default mode
Device is in factory default mode and 
requesting a profile from a distributor 
or gateway
Device is in factory default mode and is 
ready to enter site survey mode
Less than 6 months battery life left or 
not all 4 batteries are present
Device has been activated
Use SWIFT Tools to assign a profile or activate 
magnetic sensor to search for a profile.
Ensure all 4 batteries are present or replace the 
batteries
Clear the tamper condition within 
1 minute to enter site survey mode
10
5
Solid
2.5
3
0.5
1
M
18
12
5
M
Normal mode
Device is in the mesh 
Rescue mode
Device is in the mesh and looking for 
lost devices
Rescue mode
Device is in the mesh and looking for 
lost devices
Device may be in trouble
12
3
M
Refer to the panel to identify the trouble and 
possible solution