ETSI environmental and CRoHS guidelines
7368 ISAM CPE A-240Z-A Product Guide
 
 
 
3.3  Other environmental requirements 
 
Observe the following environmental requirements when handling the P-OLT or CPE 
equipment. 
 
 
3.3.1  CPE environmental requirements 
 
See the CPE technical specification documentation for more information about 
temperature ranges. 
 
 
3.3.2  Storage 
 
According to ETS 300-019-1-1 - Class 1.1, storage of OLT equipment must be in 
Class 1.1, weather-protected, temperature-controlled locations. 
 
 
3.3.3  Transportation 
 
According to EN 300-019-1-2 - Class 2.3, transportation of the OLT equipment must 
be in packed, public transportation with no rain on packing allowed. 
 
 
3.3.4  Stationary use 
 
According to EN 300-019-1-3 - Class 3.1/3.2/3.E, stationary use of OLT equipment 
must be in a temperature-controlled location, with no rain allowed, and with no 
condensation allowed. 
 
 
3.3.5  Thermal limitations 
 
When the OLT is installed in the CO or CEV, install air filters on the P-OLT. The 
thermal limitations for OLT operation in a CO or CEV are: 
• 
operating temperature: 5
C to 40C (41F to 104F) 
• 
short-term temperature: –5
C to 50C (23F to 122F) 
• 
operating relative humidity: 5% to 85% 
• 
short-term relative humidity: 5% to 95%, but not to exceed 0.024 kg of water/kg