Ever Poweline 33 15kVA/10.5kW W/PWRLTO-3315K0/00 Manuale Utente
Codici prodotto
W/PWRLTO-3315K0/00
PARAMETER/MODEL
GENERAL DATA
Output power
1)
10kVA/10kW
VFI-SS-111
Model 10k
Model 20k
Model 30k
Model 40k
Model 50k
20kVA/16kW
30kVA/24kW
40kVA/32kW
50kVA/35kW
Topology
POWERLINE 33
Total efficiency for Pmax (for VFI)
>94%
Total efficiency for Pmax (for ECO)
>98%
Cooling
Forced, internal fans
Protection level
IP20
Separate rooms with low contamination level
Overcurrent switches for base and BYPASS lines 3 x 63 A (eh.B)
Work environment
2)
Working temperature
o
10÷40 C
~
± 2 %
173 ÷ 485 Vrms
~400
± 2 %
Vrms
Synchronous / 50 Hz ± 0.2 Hz
45 ÷ 55 Hz ± 1 Hz
o
0÷40 C
Storage temperature
Relative humidity when working
< 95%
do 1000 m
< 95%
< 1%
< 1.2% for Pmax (line)
< 5% (PN-EN 62040-3)
> 0,95
Relative humidity during storage
3)
Altitude above sea level
TECHNICAL DATA
RECTIFIER
BATTERIES
MECHANICAL PARAMETERS
FITTINGS
Input voltage
Output voltage (RMS)
Output voltage waveform
Output voltage frequency
Static voltage regulation
Sine
Input voltage frequency
Power factor (PF)
Safeguard (F3, F4)
INVERTER
Output voltage distortion THDu
Protection
Crest factor CF
Maximum number of internal batteries
Maximum charge current
Maximum battery charge time
Protection
Backup time
Terminals
Signals
Communication interface
EPO
Manual BYPASS switch
Internal batteries
Internal batteries (F1)
Permitted total capacity of batteries
5:1
2 x 32
10 A
Depends on the type and number of batteries
Depends on the type and number of batteries
Depends on the type and number of batteries
2 x 200 Ah
2x 63 A / 440 VDC cylindrical 22x58 GLB
22 x 63 A / 440 VDC cylindrical 22x58 GLB (optional)
VRLA 12 V / 7Ah lub VRLA 12 V / 9 Ah
Inverter modes: short-circuit and overvoltage electronic protection.
BYPASS mode: input overvoltage protection
External batteries (F5)
Dimensions (width x depth x height)
4)
UPS weight
405x840x1040mm
270 kg
yes (NC)
yes
Screw terminals; max.
2
35 mm (wire)
Sound and LED, LCD display
RS 232, USB, network management card SNMP / HTTP (optional)
N
o
te
:
T
h
e
m
a
n
u
fa
c
tu
re
r
re
s
e
rv
e
s
t
h
e
r
ig
h
t
to
m
o
d
if
y
t
h
e
a
b
o
v
e
p
a
ra
m
e
te
rs
w
it
h
o
u
t
p
ri
o
r
n
o
ti
fi
c
a
ti
o
n
.
Notes:
1)
For standard operation, the load applied to the output must not exceed 80% of the value in the table. The power margin is necessary to ensure continuous work of the connected devices in the case of instantaneous surges of the load.
2)
Constant exposure of the battery module to temperatures of +25°C reduces the battery life.
3)
The permitted maximum load of the power supply unit decreases with the height above the sea level above the limit specified above.
4)
Weight for the typical battery set-up 1x 2x 32x VRLA 12V /7Ah. Weight depends on the type and number of batteries.
POWERLINE 3-3
10-33, 20-33, 30-33, 40-33, 50-33
www.ever.eu