Eaton TPC2365-3732 Catalogo
eaton.com/epdu 1.800.356.5794
29
(6) Indicator lights
• (1) Main power
• (1) Data light
• (4) Power on to outlets 1-4
Communications
• RS232, Serial: 9600 baud only
• Optional ethernet control via RJ45 connector (add -NET
to part number)
• Data terminal emulation software is required to communicate
with the IPC internal command codes such a telnet or
hyperterminal
EMI/RFI filtering
• Common mode - line to ground
• Differential mode - line to line
• Refer to chart 2 on page 40
Spike/surge suppression
• L-N, L-G, N-G
• Refer to chart 1 on page 40
Outlet status
Query the IPC for Outlet and Watchdog status, i.e. outlets are (on
or off)
Multiple time delay (MTD)
• Turn outlets on or off at one time
• Sequence power up and power down to outlets 1 - 4 with a
four-second time delay (factory set)
• Set power on sequence to any combination of outlets
• Set the MTD timing from one second to 999 seconds,
i.e. 009 = 9 seconds
Password protection
For added security, a password feature is included which allows
you to assign a three alphanumeric character password
Addressing
The IPC comes with a default address but you can also create your
own with any four alphanumeric characters
Watch-dog/auto-reboot
• The IPC monitors the control connection and automatically
reboot itself if the connection locks up. The auto-reboot is
activated by the time-out period running down to zero. When
this occurs the IPC shuts down all outlets for four seconds and
restart in the default or user defined sequence
• Set the time out period to any number 0-9 where each digit
represents 30 seconds, i.e. 3 = 120 seconds (user defined)
Commands available
• All outlets on/off
• Individual outlet on/off
• Set up and sequence on/off all outlets
• Create password and unit address
• Name outlets with eight character name
• Set up, enable or disable Watchdog
• Display outlet and Watchdog timer status
Intelligent Power Control IPC3400 series
Catalog Number
Full Load
Receptacles EMI/RFI
Filter
Surge
Suppression Cord (ft)
Power
Input
Plug
Serial Control
(RS232)
Ethernet
Control
Dimensions
(H x W x D, in)
IPC3400-A1
1440 VA
(4) 5-15R
15A
270V
9
5-15P
Yes
No
3.4 x 9.0 x 5.8
IPC3400-A1-NET
1440 VA
(4) 5-15R
15A
270V
9
5-15P
Yes
Yes
3.4 x 9.0 x 5.8
IPC3400-AB
1440 VA/2880 VA
(4) C13
15A
270V
8
C14
Yes
No
3.4 x 9.0 x 5.8
IPC3400-AB-NET
1440 VA/2880 VA
(4) C13
15A
270V
8
C14
Yes
Yes
3.4 x 9.0 x 5.8
Indus
trial ePDUs
Front view
Rear view
IPC3400-A1-NET